Simple mode parameter list
Basic settings
5 - 4
5.1.2
When the rated motor frequency is 60 Hz (Pr. 3)
First, check the motor rating plate. If a frequency given on the rating plate is "60 Hz" only, always set
Pr. 3 "Base frequency" to "60 Hz". Leaving the base frequency unchanged from "50 Hz" may make the
voltage low and the torque insufficient. It may result in an inverter trip due to overload.
쑶
Pr. No. Name
Initial Value
Setting
Range
Description
3
Base frequency
50 Hz
0–400 Hz
Set the rated motor frequency.
Example
쑴
Change Pr. 3 "Base frequency" to 60 Hz according to the motor rated frequency.
I001745E
Fig. 5-2:
Setting the base frequency
V/F
V/F
V/F
햲
Screen at powering on
The monitor display appears.
햳
Press the PU/EXT key to choose the PU
operation mode.
햴
Press the MODE key to choose the parameter
setting mode.
햵
Turn the digital dial until P.3 (Pr. 3) appears.
햶
Press the SET key to show the currently set value.
The initial value "50.00" appears.
햷
Turn the digital dial to change it to the setting
value of "60.00".
햸
Press the SET key to set.
Operation
Display
The parameter number
read previously appears.
Flicker ... Parameter setting complete!
PU indication is lit.
앫
By turning the digital dial, you can read another parameter.
앫
Press the SET key to show the setting again.
앫
Press the SET key twice to show the next parameter.
PRM indication is lit.
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......