Parameter overview
Parameter
6 - 10
Func-
tion
Parameter
Name
Incre-
ments
Initial
Value
Setting
Range
Description
Para-
meter-
Copy
Para-
meter
Clear
All
Para-
meter
Clear
Refer
to
Page
Rela
te
d
Paramet
ers
✔
: Enabled
—: Disabled
Retr
y func
tion a
t alarm oc
curr
enc
e
65
Retry selection
1
0
0–5
An alarm for retry can be selected.
✔
✔
✔
67
Number of retries at alarm
occurrence
1
0
0
No retry function
✔
✔
✔
1–10
Set the number of retries at alarm
occurrence. An alarm output is not provided
during retry operation.
101–110
Set the number of retries at alarm
occurrence. (The setting value minus 100 is
the number of retries.) An alarm output is
provided during retry operation.
68
Retry waiting time
0.1 s
1 s
0.1–360 s
Set the waiting time from when an inverter
alarm occurs until a retry is made.
✔
✔
✔
69
Retry count display erase
1
0
0
Clear the number of restarts succeeded by
retry.
✔
✔
✔
—
66
Refer to Pr. 22 and Pr. 23
67
–
69
Refer to Pr. 65
—
70
Refer to Pr. 30
Tab. 6-1:
Parameter overview (10)