Parameter
Frequency setting by analog input (terminal 2, 4)
FR-E700 SC EC/ENE
6 - 185
There are three methods to adjust the frequency setting voltage (current) bias/gain:
●
Method to adjust any point by application of voltage (current) to across the terminals 2-5 (4-5).
(Refer to page 6-187.)
●
Method to adjust any point without application of a voltage (current) to across terminals 2-5 (4-5).
(Refer to page 6-188.)
●
Adjusting only the frequency without adjusting the voltage (current).
(Refer to page 6-189.)
I001191E
Fig. 6-94:
Signal adjustment of terminal 2
I001191E
Fig. 6-95:
Signal adjustment of terminal 4
NOTE
When voltage/current input signal for terminal 4 was switched using Pr. 267 and voltage/current
input switch, perform calibration without fail.
Frequency setting signal
Output fr
equenc
y [H
z]
0
0
0
C3 (Pr. 902)
100%
5 V
10 V
C4 (Pr. 903)
Gain Pr. 125
Initial value
Bias
50 Hz
C2
(Pr. 902)
Frequency setting signal
Output fr
equenc
y [H
z]
0
0
C6 (Pr. 904)
100%
20 mA
C7 (Pr. 905)
Gain Pr. 126
Initial value
Bias
50 Hz
C5
(Pr. 904)
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......