Frequency setting by analog input (terminal 2, 4)
Parameter
6 - 188
2. Method to adjust any point without application of a voltage (current) to across terminals 2-5 (4-5).
(This example shows how to change from 4 V to 5 V, assuming that Pr. 241 is set to "1".)
I001887E
Fig. 6-97:
Bias and gain adjustment without application of an reference signal
NOTE
By pressing the digital dial after step
햷
, you can confirm the current frequency setting bias/gain
setting. It cannot be confirmed after execution of step
햸
.
Operation
Display
Analog voltage (current) value (%)
across terminals 2-5 (across terminals
4-5) and the "A" indication or no
indication is lit.
The gain frequency is reached when a
voltage of 5.0 V is displayed.
Flicker ... Parameter setting complete!
(Adjustment completed)
앫
By turning the digital dial, you can read another parameter.
앫
Press the SET key to return to the "C---" indication (step
햵
).
앫
Press the SET key twice to show the next parameter (Pr.CL).
햲
Confirmation of the RUN indication and
operation mode indication.
The inverter must be at a stop.
The inverter must be in the PU operation
mode (using the PU/EXT key).
햳
Press the MODE key to choose the
parameter setting mode.
햴
Turn the digital dial until "C..." appears.
햵
Press the SET key until "C---" appears.
햶
Turn the digital dial until "C 4 (C 7)"
appears. Set to C4 "Terminal 2 frequency
setting gain".
햷
Press the SET key to display the analog
voltage (current) value (%).
햸
Turn the digital dial to set the gain of the
voltage signal value. If Pr. 241 is set to "1"
the value will be displayed directly.
CAUTION:
When you start turning the digital dial
the value that is currently stored
(in this example 4 V) will be displayed.
햹
Press the SET key to set.
PRM indication is lit.
The parameter number read
previously appears.
C1 to C7 setting is enabled.
Voltage input
Current input
Voltage
input
Current
input
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......