Parameter
Communication operation and setting
FR-E700 SC EC/ENE
6 - 281
●
Fault history
Register
Definition
Read/Write
Remarks
40501
Fault history 1
Read/write
Being 2 bytes in length, the data is stored as "H00
첸첸
".
The error code can be referred to in the low-order 1 byte.
Performing write using the register 40501 batch-clears
the alarm history. Set any value as data.
40502
Fault history 2
Read
40503
Fault history 3
Read
40504
Fault history 4
Read
40505
Fault history 5
Read
40506
Fault history 6
Read
40507
Fault history 7
Read
40508
Fault history 8
Read
Tab. 6-105:
Fault history
Data
Description
Data
Description
Data
Description
H00
No fault present
H70
E.BE
HC7
E.AIE
H10
E.OC1
H80
E.GF
HC8
E.USB
H11
E.OC2
H81
E.LF
HC9
E.SAF
H12
E.OC3
H90
E.OHT
HD8
E.MB4
H20
E.OV1
HA0
E.OPT
HD9
E.MB5
H21
E.OV2
HA1
E.OP1
HDA
E.MB6
H22
E.OV3
HB0
E.PE
HDB
E.MB7
H30
E.THT
HB1
E.PUE
HF1
E.1
H31
E.THM
HB2
E.RET
HF5
E.5
H40
E.FIN
HB3
E.PE2
HF6
E.6
H52
E.ILF
HC0
E.CPU
HF7
E.7
H60
E.OLT
HC5
E.IOH
HFD
E.13
Tab. 6-106:
Fault code list
NOTE
Refer to section 7.1 for details of fault definition.
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......