Enclosure design
Installation
2 - 12
Arrangement of multiple inverters
When multiple inverters are placed in the same enclosure, generally arrange them horizontally as
shown in the figure (a). When it is inevitable to arrange them vertically to minimize space, take such
measures as to provide guides since heat from the bottom inverters can increase the temperatures in
the top inverters, causing inverter failures.
Placement of ventilation fan and inverter
Heat generated in the inverter is blown up from the bottom of the unit as warm air by the cooling fan.
When installing a ventilation fan for that heat, determine the place of ventilation fan installation after
fully considering an air flow. (Air passes through areas of low resistance. Make an airway and airflow
plates to expose the inverter to cool air.)
I001006E
Fig. 2-11:
Arrangement of multiple inverters
NOTE
When mounting multiple inverters, fully take caution not to make the ambient temperature of the
inverter higher than the permissible value by providing ventilation and increasing the enclosure
size.
I001007E
Fig. 2-12:
Placement of ventilation fan and inverter
a) Horizontal arrangement
b) Vertical arrangement
Inverter
Inverter
Inverter
Inverter
Inverter
Inverter
Guide
Guide
Guide
Enclosure
Enclosure
Good example!
Inverter
Inverter
Bad example!
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......