Operation panel
Operation
4 - 14
I001739E
Fig. 4-9:
Operation lock
햲
Screen at powering on
The monitor display appears.
햳
Press the PU/EXT key to choose the PU
operation mode.
햴
Press the MODE key to choose the parameter
setting mode.
햵
Turn the digital dial until P.161 (Pr. 161) appears.
햶
Press the SET key to show the currently set value.
The initial value "0" appears.
햷
Turn the digital dial clockwise to change it
to the setting value of "10".
햸
Press the SET key to set.
햹
Press the MODE key for 2 s to show the key lock
mode.
Operation
Display
The parameter number read previously
appears.
Flicker ... Parameter setting complete!
PU indication is lit.
PRM indication is lit.