PU operation mode
Basic settings
5 - 28
5.2.5
Perform frequency setting by analog current input
An external current source is connection to the frequency inverter for setpoint default setting.
●
Pr. 79 "Operation mode selection" must be set to "4" (external/PU combined operation mode 2).
●
Turn the AU signal on.
●
Use the RUN key to give a start command.
I001773E
Fig. 5-19:
Frequency setting by analog current input
NOTE
For the analog current input (0/4 to 20 mA) to become effective for setpoint default setting, the AU
signal on the AU terminal must be activated. This is done, for example, by means of a bridge as
shown in Fig. 5-19.
Power supply
Motor
Inverter
Current signal
source
(0/4–20 mA DC)
AU signal