Parameter overview
Parameter
6 - 4
Func-
tion
Parameter
Name
Incre-
ments
Initial
Value
Setting
Range
Description
Para-
meter-
Copy
Para-
meter
Clear
All
Para-
meter
Clear
Refer
to
Page
Rela
te
d
Paramet
ers
✔
: Enabled
—: Disabled
DC injec
tion br
ak
e
10
DC injection brake operation
frequency
0.01 Hz
3Hz
0–120 Hz
Set the operation frequency of the DC
injection brake.
✔
✔
✔
11
DC injection brake operation
time
0.1 s
0.5s
0
DC injection brake disabled
✔
✔
✔
0.1–10 s
Set the operation time of the DC injection
brake.
12
DC injection brake operation
voltage
0.1%
6/4/2% *
0
DC injection brake disabled
✔
✔
✔
0.1–30 %
Set the DC injection brake voltage (torque).
* Initial values differ according to the inverter
capacity:
FR-E720S-008SC and 015SC/
FR-E720S-030SC to 110SC,
FR-E740-016SC to 170SC/
FR-E740-230SC and 300SC
Star
ting
frequenc
y
13
Starting frequency
0.01 Hz
0.5Hz
0–60 Hz
Starting frequency can be set.
✔
✔
✔
571
Holding time at a start
0.1 s
9999
0.0–10.0 s
Set the holding time of Pr. 13 "Starting
frequency".
✔
✔
✔
9999
Holding function at start is invalid.
V/F pa
tt
ern ma
tching
applica
tions
14
Load pattern selection
1
0
0
For constant torque load
✔
✔
✔
1
For variable-torque load
2
For constant
torque elevators
at reverse rotation
boost of 0%
3
at forward rotation
boost of 0%
Jog oper
ation
15
Jog frequency
0.01 Hz
5Hz
0–400 Hz
Set the frequency for jog operation.
✔
✔
✔
16
Jog acceleration/
deceleration time
0.1/
0.01 s
0.5s
0–3600/
360 s
Set the acceleration/deceleration time for
jog operation. Set the time taken to reach
the frequency set in Pr. 20 "Acceleration/
deceleration reference frequency" for
acceleration/deceleration time (initial value
is 50 Hz).
In addition, acceleration/deceleration time
can not be set separately.
✔
✔
✔
MRS input
selec
tion
17
MRS input selection
1
0
0
Open input always
✔
✔
✔
2
Normally closed input
(NC contact input specifications)
4
External terminal: Normally closed input
(NC contact input specifications)
Communication: Normally open input
—
18
Refer to Pr. 1 and Pr. 2
19
Refer to Pr. 3
20
21
Refer to Pr. 7 and Pr. 8
Tab. 6-1:
Parameter overview (4)
V/FV/FV/F
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......