Communication operation and setting
Parameter
6 - 282
Communication error count (Pr. 343)
You can check the cumulative number of communication errors.
Output terminal LF "alarm output (communication error warnings)"
During a communication error, the alarm signal (LF signal) is output by open collector output. Assign
the used terminal using any of Pr. 190 to Pr. 192 "Output terminal function selection".
Parameters
Setting Range
Minimum Setting Range
Initial Value
343
(Read only)
1
0
Tab. 6-107:
Number of communication errors
NOTE
The number of communication errors is temporarily stored into the RAM. As it is not stored into
the E²PROM, performing a power supply reset or inverter reset clears the value to 0.
I001229E
Fig. 6-134:
Output of the LF signal
NOTE
The LF signal can be assigned to the output terminal using any of Pr. 190 to Pr. 192. Changing the
terminal assignment may affect the other functions. Make setting after confirming the function of
each terminal.
Master
Slave
Communication
Error count
(Pr. 343)
Signal LF
Alarm data
Alarm data
Normal data
Reply data
Normal data
Alarm data
Reply data
OFF
OFF
OFF
ON
ON
Communication error count is increased in
synchronization with leading edge of LF signal
Turns off when normal data is received
Alarm data:
Data resulting in
communication error.
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......