Parameter
Communication operation and setting
FR-E700 SC EC/ENE
6 - 275
●
Error response
An error response is returned if the query message received from the master has an illegal
function, address or data. No response is returned for a parity, CRC, overrun, framing or busy error.
Error response (Response message)
햲
An error will not occur in the following cases:
– Function code H03 (Read Holding Register Data )
When the No. of Points is 1 or more and there is one or more holding registers from which data
can be read.
– Function code H10 (Write Multiple Holding Register Data)
When the No. of Points is 1 or more and there is 1 or more holding registers to which data can
be written.
Namely, when the function code H03 or H10 is used to access multiple holding registers, an error
will not occur if a non-existing holding register or read disabled or write disabled holding register
is accessed.
NOTE
No response message is sent in the case of broadcast communication also.
���
Slave Address
���
Function
���
Exception Code
CRC Check
(8 bits)
H80 + Function
(8 bits)
(8 bits)
L
(8 bits)
H
(8 bits)
Message
Description
���
Slave address
Set the address received from the master.
���
Function
The master-requested function code + H80 is set.
���
Exception code
The code in the following table is set.
Tab. 6-97:
Description of response data
Code
Error Item
Description
01
ILLEGAL FUNCTION
(Function code illegal)
The set function code in the query message from the master cannot be handled
by the slave.
02
ILLEGAL DATA ADDRESS
햲
(Address illegal)
The set register address in the query message from the master cannot be han-
dled by the inverter.
(No parameter, parameter read disabled, parameter write disabled)
03
ILLEGAL DATA VALUE
(Data illegal)
The set data in the query message from the master cannot be handled by the
inverter.
(Out of parameter write range, mode specified, other error)
Tab. 6-98:
Error code list
NOTES
An error will occur if all accessed holding registers do not exist.
Data read from a non-existing holding register is 0, and data written there is invalid.
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......