Communication operation and setting
Parameter
6 - 270
Query message
Normal response (Response message)
Read value:
Register 41004 (Pr. 4): H1770 (60.00 Hz)
Register 41005 (Pr. 5): H0BB8 (30.00 Hz)
Register 41006 (Pr. 6): H03E8 (10.00 Hz)
쑶
Example
쑴
To read the register values of 41004 (Pr. 4) to 41006 (Pr. 6) from the slave address 17 (H11).
Slave Address
Function
Starting Address
No. of Points
CRC Check
H11
(8 bits)
H03
(8 bits)
H03
(8 bits)
HEB
(8 bits)
H00
(8 bits)
H03
(8 bits)
H77
(8 bits)
H2B
(8 bits)
Slave Address
Function
Byte Count
Data
CRC Check
H11
(8 Bits)
H03
(8 Bits)
H06
(8 Bits)
H17
(8 Bits)
H70
(8 Bits)
H0B
(8 Bits)
HB8
(8 Bits)
H03
(8 Bits)
HE8
(8 Bits)
H2C
(8 Bits)
HE6
(8 Bits)