Common specifications
Appendix
A - 4
햲
This operation guide is only available with option parameter unit (FR-PU07).
햳
This protective function is available with the three-phase power input specification model only.
햴
This protective function does not function in the initial status.
햵
When using the inverters at the ambient temperature of 40 °C or less, the inverters can be installed
closely attached (0 cm clearance).
햶
The product may only be exposed to the full extremes of this temperature range for short periods
(e.g. during transportation).
Displa
y
Operation panel
or
Parameter unit (FR-PU07)
Operating status
The following operating status can be displayed: output frequency, motor current (steady), output voltage, frequency setting,
cumulative energization time, actual operation time, motor torque, converter output voltage, regenerative brake duty,
electronic thermal relay function load factor, output current peak value, converter output voltage peak value, motor load
factor, PID set point, PID measured value, PID deviation, inverter I/O terminal monitor, I/O terminal option monitor, output
power, cumulative power, motor thermal load factor, and inverter thermal load factor.
Fault record
Fault record is displayed when a fault occurs.
Past 8 fault records (output voltage/current/frequency/cumulative energization time right before the fault occurs) are stored.
Additional display by the
parameter unit
(FR-PU04/FRPU07) only
Operating status
Not used
Fault record
Output voltage/current/frequency/cumulative energization time immediately before the fault occurs
Interactive guidance
햲
Operation guide/trouble shooting with a help function
Pr
ot
ec
tion
Protective functions
Overcurrent during acceleration, overcurrent during constant speed, overcurrent during deceleration, overvoltage during
acceleration, overvoltage during constant speed, overvoltage during deceleration, inverter protection thermal operation,
motor protection thermal operation, heatsink overheat, input phase failure
햳
, output side earth (ground) fault overcurrent at
start, output phase failure, external thermal relay operation
햴
, option fault
햴
, parameter error, internal board fault, PU
disconnection, retry count excess
햴
, CPU fault, brake transistor alarm, inrush resistance overheat, communication error,
analog input error, USB communication error, brake sequence error 4 to 7
햴
, safety circuit fault
Warning functions
Fan alarm (FR-E720S-050SC or more, FR-E740-040SC or more), overcurrent stall prevention, overvoltage stall prevention, PU
stop, parameter write error, regenerative brake prealarm
햴
, electronic thermal relay function prealarm, maintenance
output
햴
, undervoltage, operation panel lock, password locked, inverter reset, safety stop
En
vir
onmen
t
Ambient temperature
10 °C to +50 °C (non-freezing)
햵
Storage temperature
햶
20 °C to +65 °C
Ambient humidity
Max. 90% (non-condensing)
Ambience conditions
For indoor use only, avoid environments containing corrosive gases, install in a dust-free location.
Altitude
Max. 1000 m above sea level
Vibration resistance
Max. 5.9 m/s² (JIS 60068-2-6) or less at 10 to 55 Hz (directions of X, Y and Z axes)
FR-E700SC
Specification
Tab. A-3:
Common specifications (2)
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......