Misoperation prevention and parameter setting restriction
Parameter
6 - 194
Restart (PS reset) method when PU stop (PS display) is made during PU operation
PU stop (PS display) is made when the motor is stopped from the unit where control command source
is not selected (operation panel, parameter unit (FR-PU04/FR-PU07, operation panel for FR-E500
(PA02)) in the PU operation mode.
For example, when Pr. 551 "PU mode operation command source selection" = 9999 (initial value), the
motor is stopped from the PU (PS display) if entered from the operation panel in PU operation mode
with the parameter unit mounted.
When the motor is stopped from the PU when the parameter unit (FR-PU04/FR-PU07) is select-
ed as control command source
햲
After the motor has decelerated to a stop, press the STOP/RESET key of the parameter unit
(FR-PU04/FR-PU07).
햳
Press the PU/EXT key to change to the external operation mode. The EXT indication is lit. The
message "PS" is cancelled.
햴
Press the PU key of the parameter unit (FR-PU04/FR-PU07) to select the PU operation mode.
햵
Press the FWD or the REV key of the parameter unit (FR-PU04/FR-PU07).
NOTE
When Pr. 551 = "9999", the priorities of the PU control source is USB connector > parameter unit
(FR-PU04/FR-PU07) > operation panel.
P
CAUTION:
Do not reset the inverter while the start signal is being input. Otherwise, the motor will start
instantly after resetting, leading to potentially hazardous conditions.
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......