Parameter
CC-Link IE Field Network Basic
FR-E700 SC EC/ENE
6 - 371
Setting the running frequency
The following program example changes the running frequency of station 1 inverter to 50.00 Hz.
●
Set frequency: K5000 decimal
The reply code at the time of instruction code execution is set to D2.
(For information about the reply code (RWr2) refer to page 6-360.)
I003136E
Fig. 6-183:
Program example 7
NOTES
To continuously change the running frequency from the programmable controller
When the frequency (speed) setting completion (example: X100D) switches on, make sure that the
reply code in the remote register is 0000H and change the set data (example: W101) continuously.
Program example for writing data to E²PROM
Modify the program in fig. 6-183 as follows:
●
Frequency setting command Y100D
씮
Y100E
●
Frequency setting completion X100D
씮
X100E
(0)
SM1536
SD1536.0
SD1540.0
M0
(4)
M0
X20
PLS
M300
(8)
M300
SET
M301
(10)
M301
X100D
MOV
K5000
W101
SET
Y100D
RST
M301
SET
M302
(17)
M302
X100D
MOV
W2
D2
RST
Y100D
RST
M302
(23)
END
Check the data link status of the station 1
Read reply code (RWr2) to D2 when the frequency
setting completion (RX0D) turns on.
Write set frequency to RWw1.
Turn off the frequency setting command RAM
(RY0D)
Turn off the frequency setting command RAM
(RY0D)
Timing chart when writing to RAM
Timing chart when writing to E²PROM
Y100D
W101
Inverter running
frequency
Y100E
W101
Inverter running
frequency
햳
햲
Reflect to the inverter when Y100E turns on
햲
For E²PROM, write is made only once when Y100E is switched on.
햳
If the set data is changed with Y100E on, it is not reflected on the inverter.
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......