background image

Installation Guide

VLT® 24 V DC Supply MCB 107

VLT® Series FC 102, FC 103, FC 202, and FC 301/FC
302

1 Scope of Delivery, Safety, and Installation

1.1 Purpose of the Manual

This installation guide describes the installation of the VLT

®

 24 V DC Supply MCB 107.

1.2 Purpose of the VLT® 24 V DC Supply MCB 107

VLT

®

 24 V DC Supply MCB 107 option is a low voltage supply to the control card or any option card installed. This option keeps the

control section (including parameter configurations) and any installed option alive during a power failure.

NOTICE

External power supply

To achieve the intended functionality, an external 24 V DC supply as specified below has to be connected to the terminals of
the option.

Specifications for VLT 24 V DC Supply MCB 107

Specification

Value

Input voltage range

24 V DC ±15% (maximum 37 V for 10 s)

Maximum input current

2.2 A

Average input current for FC 301/FC 302

0.9 A

Maximum cable length

75 m (246 ft)

Input capacitance load

<10 uF

Power-up delay

<0.6 s

Connection terminals

Terminal 35: - external 24 V DC supply

Terminal 36: + external 24 V DC supply

AN287957936346en-000101 / 130R0308 | 1