Safety instructions

WARNING!

 Obey these instructions. If you ignore them, injury or death, 

or damage to the equipment can occur. If you are not a qualified 

electrical professional, do not do electrical installation or maintenance 

work.

• 

Do not do work on the drive, motor cable, motor, or control cables when the 

drive is connected to the input power. Before you start the work, isolate the 

drive from all dangerous voltage sources and make sure that it is safe to 

start the work. Always wait for 5 minutes after disconnecting the input 

power to let the intermediate circuit capacitors discharge.

• 

Do not do work on the drive when a rotating permanent magnet motor is 

connected to it. A rotating permanent magnet motor energizes the drive, 

including its input and output terminals.

1.  Unpack the delivery

Keep the drive in its package until you are ready to install it. After unpacking, 

protect the drive from dust, debris and moisture. 
Make sure that these items are included:

• 

drive

• 

assistant control panel

• 

options, if ordered

• 

RIIO-01 I/O & EIA-485 module. 

Note:

 If a fieldbus adapter is ordered, it 

replaces the RIIO-01 module of the standard delivery.

• 

mounting template (frames R3 and R4 only)

• 

installation accessories (cable clamps, etc.)

• 

multilingual warning sticker sheet (residual voltage warning)

• 

safety instructions

• 

quick installation and start-up guide

• 

hardware and firmware manuals, if ordered.

Make sure that there are no signs of damage to the items.

2.  Reform the capacitors

If the drive has not been powered up for a year or more, you must reform the DC 

link capacitors. The manufacturing date is on the type designation label. Refer 

to 

Capacitor reforming instructions

 (

3BFE64059629 [English]

).

3.  Select the cables and fuses

• 

Select the power cables. Obey the local regulations.

Input power cable:

 ABB recommends to use symmetrical shielded cable 

(VFD cable) for the best EMC performance.

Motor cable:

 Use symmetrical shielded cable (VFD cable) for the best EMC 

performance. Symmetrical shielded cable also reduces bearing currents, 

wear, and stress on motor insulation.

Power cable types:

 In IEC installations, use copper or aluminum cables (if 

permitted). In UL installations, use only copper cables.

Current rating:

 max. load current.

Voltage rating:

 min. 600 V AC.

Temperature rating:

 In IEC installations, select a cable rated for at least 

70

 

°C (158

 

°F) maximum permissible temperature of conductor in 

continuous use. In UL installations, select a cable rated for at least 75

 

°C 

(167

 

°F).

Size: 

Refer to 

Fuses and typical power cable sizes

 for the typical cable 

sizes and to 

Terminal data for the power cables

 for the maximum cable 

sizes.

• 

Select the control cables. Use double-shielded twisted-pair cable for analog 

signals. Use double-shielded or single-shielded cable for the digital, relay and 

I/O signals. Do not run 24 V and 115/230 V signals in the same cable.

• 

Protect the drive and input power cable with the correct fuses. Refer to 

Fuses and typical power cable sizes

.

4.  Examine the installation area

The drive is intended for cabinet installation and has a degree of protection of 

IP20 / UL open type.
Examine the site where you will install the drive. Make sure that:

• 

The installation site is sufficiently ventilated and hot air does not recirculate.

• 

There is sufficient free space around the drive for cooling, maintenance, and 

operation. For the minimum free space requirements, refer to 

Free space 

requirements

.

• 

The ambient conditions meet the requirements. Refer to 

Ambient 

conditions

.

• 

The installation surface is as close to vertical as possible and strong enough 

to support the weight of the drive. Refer to 

Dimensions and weights

.

• 

The installation surface, floor and materials near the drive are not flammable.

• 

There are no sources of strong magnetic fields, such as high-current single-

core conductors or contactor coils near the drive. A strong magnetic field 

can cause interference in the operation of the drive.

5.  Install the drive

You can install the drive with screws, or to a DIN rail (top hat type, width × height 

= 35 mm × 7.5 mm [1.4 in × 0.3 in]).

• 

Install R0 drives vertically. R0 drives do not have a cooling fan.

• 

You can install drives with frame size R1…R4 tilted by a maximum of 

90 degrees, from vertical to fully horizontal orientation. 

• 

Do not install the drive upside down.

• 

You can install several drives side by side.

ABB DRIVES FOR HVAC

ACH480 drives

Quick installation and start-up guide 

To install the drive with screws

1. Make marks onto the surface for the 

mounting holes. Refer to 

Dimensions and 

weights

. Use the included mounting 

template for frames R3 and R4.

2. Drill the holes for the mounting screws. If 

necessary, install suitable plugs or 

anchors into the holes.

3. Install the mounting screws into the 

holes. Leave a gap between the screw 

head and installation surface.

4. Put the drive onto the mounting screws.
5. Tighten the mounting screws.

To install the drive to a DIN rail

1. Move the locking part to the left.

 

If 

necessary, use a flat-head screwdriver.

2. Push and hold the locking button down.
3. Put the top tabs of the drive onto the top 

edge of the DIN rail.

4. Put the drive against the bottom edge of 

the DIN rail.

5. Release the locking button.
6. Move the locking part to the right.
7. Make sure that the drive is correctly 

installed.

To remove the drive, open the locking part 

and lift the drive from the DIN rail.

6.  Measure the insulation resistance

Drive:

 Do not do voltage tolerance or insulation resistance tests on the drive, 

because this can cause damage to the drive.

Input power cable:

 Before you connect the input power cable, measure the 

insulation of the input power cable. Obey the local regulations.

Motor and motor cable

:

1. Make sure that the motor cable is connected to the motor and disconnected 

from the drive output terminals T1/U, T2/V and T3/W.

2. Use a voltage of 1000 V DC to measure the 

insulation resistance between each phase 

conductor and the protective earth 

conductor. The insulation resistance of an 

ABB motor must be more than 100 Mohm (at 

25 °C [77 °F]). For the insulation resistance of 

other motors, refer to the manufacturer’s 

documentation. Moisture in the motor 

decreases the insulation resistance. If you 

think that there is moisture in the motor, dry the motor and do the 

measurement again.

7.  Make sure that the drive is compatible with the 

grounding system

You can connect all drive types to a symmetrically grounded TN-S system 

(center-grounded wye). The drive is delivered with the EMC and VAR screws 

installed. The material of the screws (plastic or metal) depends on the product 

variant. The table shows when to remove the metal EMC screw (disconnect the 

internal EMC filter) or metal VAR screw (disconnect the varistor circuit).

8.  Connect the power cables

Connection diagram (shielded cables)

1. Disconnecting device.
2. Two protective earth (ground) conductors. Drive safety standard 

IEC/EN 61800-5-1 requires two PE conductors, if the cross-sectional area of 

the PE conductor is less than 10 mm

2

 Cu or 16 mm

2

 Al. For example, you can 

use the cable shield in addition to the fourth conductor. 

3. Use a separate grounding cable or a cable with a separate PE conductor for 

the line side, if the conductivity of the fourth conductor or shield does not 

meet the requirements for the PE conductor.

4. Use a separate grounding cable for the motor side, if the conductivity of the 

shield is not sufficient, or if there is no symmetrically constructed PE 

conductor in the cable.

5. 360-degree grounding of the cable shield is required for the motor cable and 

brake resistor cable (if used). It is also recommended for the input power 

cable.

6. Brake resistor and resistor cable (optional).

Connection procedure (shielded cables)

For the tightening torques, refer to 

Terminal data for the power cables

.

1. Loosen the screw on the front cover. 

Then lift the front cover up.

2. Attach the residual voltage warning 

sticker in the local language to the drive. 

3. Strip the motor cable.
4. Ground the motor cable shield under the 

grounding clamp.

5. Twist the motor cable shield into a 

bundle, mark it and connect it to the 

grounding terminal.

Screw 

label

Factory default 

screw material

Grounding systems

Symmetrically 

grounded TN-S 

systems (center-

grounded wye)

Corner-grounded 

delta, midpoint-

grounded delta and 

TT systems

IT systems 

(ungrounded or 

high-resistance 

grounded)

EMC

Metal

Do not remove

Remove

Remove

Plastic

 1)

1) UL (NEC) types have a plastic EMC screw.

Do not remove

 2)

2) Can install the metal screw (included in the drive delivery) to connect the internal EMC filter.

Do not remove

Do not remove

VAR

Metal

Do not remove

Do not remove

Remove

Plastic

Do not remove

Do not remove

Do not remove

W

H

M1

M2

U1

V1

W1

PE

M
3~

ohm

U1-PE, V1-PE, W1-PE

PE

PE

L1

L2

L3

R-

R+

UDC+ UDC-

U1

W1

M

PE

3

T1/

U

T2/

V

T3/

W

V1

L1

L2

L3

(L)

(N)

ACH480

2

3

4

6

5

1

6. Connect the phase conductors of the 

motor cable to terminals T1/U, T2/V and 

T3/W.

7. If used, connect the brake resistor cable 

to terminals R- and UDC+. Use a shielded 

cable and ground the shield under the 

grounding clamp.

8. Make sure that the R- and UDC+ terminal 

screws are tightened. Do this step also if 

you do not connect cables to the 

terminals.

9. Strip the input power cable. 
10. If the input power cable has a shield, 

ground the shield under the grounding 

clamp. Then twist the shield into a 

bundle, mark it and connect it to the 

grounding terminal.

11. Connect the PE conductor of the input 

power cable to the grounding terminal. If necessary, use a second PE 

conductor. 

12. In 3-phase drives, connect the phase conductors of the input power cable to 

terminals L1, L2 and L3. In 1-phase drives, connect the phase and neutral 

conductors to terminals L1 and L2.

13. Mechanically attach the cables on the outside of the drive.

9.  Install the communication module

To install the communication module (I/O 

module or fieldbus module):
1. Pull out the locking tab of the 

communication module.

2. Align the communication module 

contacts with the contacts on the drive. 

Carefully push the module into position.

3. Push in the locking tab of the 

communication module.

4. Tighten the locking screw to fully attach 

and electrically ground the 

communication module.

10.  Connect the control cables

Keep the signal wire pairs twisted as near to the terminals as possible to 

prevent inductive coupling. The tightening torque for the terminal connections 

is 0.5 … 0.6 N·m (4.4 … 5.3 lbf·in).
1. Strip a part of the outer shield of the 

control cable for grounding.

2. Use a cable tie to ground the outer shield 

to the grounding tab.

3. Strip the control cable conductors.
4. Connect the conductors to the correct 

control terminals. 

5. Connect the shields of the twisted pairs 

and grounding wires to the SCR terminal.

6. Mechanically attach the control cables on 

the outside of the drive.

Default I/O connections (HVAC default) 

Embedded fieldbus connection

You can connect the drive to an EIA-485 serial communication link through the 

embedded fieldbus interface on the RIIO-01 module. The embedded fieldbus 

interface supports the BACnet MS/TP, Modbus RTU, and N2 protocols. 
To configure EIA-485 communication with the embedded fieldbus:
1. Connect the fieldbus cables and the necessary I/O signals.
2. Use the termination switch to set the correct termination.
3. Power up the drive and set the necessary parameters.
A connection example is shown below.

1) The devices at the ends of the fieldbus must have termination set to ON. All other devices 

must have termination set to OFF (1).

2) Attach the cable shields together at each drive, but do not connect them to the drive. 

Connect the shields only to the grounding terminal in the automation controller.

3) Connect the signal ground (DGND) conductor to the signal ground reference terminal in 

the automation controller. If the automation controller does not have a signal ground 

reference terminal, you can connect the signal ground to the cable shields through a 

100 ohm resistor, preferably near the controller.

Terminal

Description

 1)

1) × = on base unit, empty = on RIIO-01 I/O extension module

Reference voltage and analog I/O

1

SCR Signal cable shield (screen)

2

AI1

Output freq./speed reference: 0 … 10 V

3

AGND Analog input circuit common

4

+10 V Reference voltage 10 V DC

5

AI2 Actual feedback: 0 … 20 mA

6

AGND Analog input circuit common

7

AO1 Output frequency: 0 … 20 mA

8

AO2 Output current: 0 … 20 mA

9

AGND Analog output circuit common

Aux. voltage output and programmable digital inputs

10

+24 V Aux. voltage 24 V DC, max. 250 mA

11 DGND Aux. voltage output common

12 DCOM Digital input common for all

13

DI1

Stop (0)/Start (1)

14

DI2 Not configured

15

DI3 Constant frequency/speed selection

16

DI4 Start interlock 1 (1 = allow start)

17

DI5 Not configured

18

DI6 Not configured

Relay outputs

19

RO1C

Damper control

20

RO1A

250 V AC / 30 V DC

21

RO1B

2 A

22 RO2C

Running

23

RO2A

250 V AC / 30 V DC

24

RO2B

2 A

25

RO3C

Fault (-1)

26

RO3A

250 V AC / 30 V DC

27

RO3B

2 A

Safe torque off

34 SGND Safe torque off (STO). Both circuits must be closed for the 

drive to start. The drawing shows the simplified 

connection of a safety circuit through safety contacts. If 

STO is not used, leave the factory-installed jumpers in 

place. See also section 

Safe torque off (STO)

.

35

IN1

36

IN2

37

OUT1

1

2

3

4

1 … 10 kohm

Max. 500 ohm

G

R

-

+

B+

A-

DGND

B+

A-

DGND

ON

1

B+

A-

DGND

ON

1

ON

1

Automation 

controller

Termination ON

1)

Drive

Termination OFF

Drive

Termination ON

1)

Drive

Termination OFF

3)

2)