This guide is applicable to the global IEC and NEC North American installations

.

Safety instructions

WARNING!

 Obey these instructions. If you ignore them, injury or death, or damage to the equipment can occur. If 

you are not a qualified electrical professional, do not do electrical installation or maintenance work.

WARNING!

 If you activate the automatic fault reset or automatic restart functions of the drive control program, 

make sure that no dangerous situations can occur. These functions reset the drive automatically and continue 

operation after a fault or supply break. If these functions are activated, the installation must be clearly marked as 

defined in IEC/EN/UL 61800-5-1, subclause 6.5.3, for example, “THIS MACHINE STARTS AUTOMATICALLY”.

• 

Do not do work on the drive, motor cable, motor, or control cables when the drive is connected to the input power. 

Before you start the work, isolate the drive from all dangerous voltage sources and measure that there are no 

dangerous voltages. Always wait for 5 minutes after disconnecting the input power to let the intermediate circuit 

capacitors discharge.

• 

Do not do work on the drive when a rotating permanent 

magnet motor is connected to it. A rotating permanent 

magnet motor energizes the drive, including its input and 

output terminals.

• 

Make sure that debris from drilling, cutting and grinding. 

does not enter the drive.

• 

Frames R6 and R8: Use the lifting eyes of the drive when 

you lift the drive. Do not tilt the drive. The drive is heavy 

and its center of gravity is high. An overturning drive can 

cause physical injury.

1. Unpack the drive

Keep the drive in its package until you are ready to install it. After unpacking, protect the drive from dust, debris and 

moisture. Make sure that these items are included:  drive, mounting template, control panel, quick installation and start-up 

guide, multilingual residual voltage warning stickers, hardware and firmware manuals (if ordered), options in separate 

packages (if ordered). Make sure that there are no signs of damage to the items.

2.  Reform the capacitors

If the drive has not been powered up for a year or more, you must reform the DC link capacitors. See 

Related documents

 or 

contact ABB technical support.

Documentation in other languages Ecodesign information (EU 2019/1781 

and SI 2021 No. 745)

 

About this document

3AXD50000803057 Rev A EN 

2021-09-01

© 2021 ABB. All rights reserved. 

Original instructions.

DRIVES FOR WATER

ACQ580-31

Quick installation and start-up guide 

Summary of Contents for ACQ580-31 Series

Page 1: ...ive when a rotating permanent magnet motor is connected to it A rotating permanent magnet motor energizes the drive including its input and output terminals Make sure that debris from drilling cutting...

Page 2: ...pair cable for analog signals Use double shielded or single shielded cable for the digital relay and I O signals Do not run 24 V and 115 230 V signals in the same cable Protect the drive and input pow...

Page 3: ...creases the insulation resistance If you think that there is moisture dry the motor and do the measurement again Frame Symmetrically grounded TN S systems center grounded wye Corner grounded delta and...

Page 4: ...l area of the PE conductor is less than 10 mm2 Cu or 16 mm2 Al For example you can use the cable shield in addition to the fourth conductor PE PE L1 L2 L3 UDC U1 W1 M 3 T1 U T2 V T3 W V1 PE PE L1 L2 L...

Page 5: ...strated in the applicable figure 3c Slide the cables through the holes in the cable entry and attach the grommets to the holes 4 Connect the power cables For the tightening torques refer to Terminal d...

Page 6: ...ound the motor cable shield at the motor end For minimum radio frequency interference ground the motor cable shield 360 degrees at the cable entry of the motor terminal box 4b 4c 2 9 N m 2 9 N m 2 N m...

Page 7: ...SCR1 terminal 3 Tie all control cables to the provided cable tie mounts Default I O connections Water default Total load capacity of the auxiliary voltage output 24V X2 10 is 6 0 W 250 mA 24 V DC Term...

Page 8: ...cluded in the delivery 12 Install the cover s 1 7 N m R3 R8 R6 1 7 N m 15 lbf in 2 N m 1 5 lbf ft 2 N m 2 N m 2 N m 1 5 lbf ft 1 2 1 2 IP21 UL Type 1 R3 IP55 UL type 12 R3 IP21 UL type 1 R6 R8 IP55 UL...

Page 9: ...cable shield and connect them to the grounding terminals Ground the shield 360 degrees at the grounding clamp If you use discrete conductors connect the insulated ground conductor to the ground termin...

Page 10: ...Home screen press Menu to enter the Main Menu 5 In the Main menu go to Parameters Complete list 95 HW configuration pressing Select repeatedly to select parameter 95 01 6 In parameter 95 01 Supply vol...

Page 11: ...Communication control Refresh settings Validates any changed EFB configuration settings Use this after changing any parameters in group 58 58 14 Communication loss action 58 17 Transmit delay 58 28 EF...

Page 12: ...hree current carrying conductors in raceway or cable or earth directly buried For other conditions size the cables according to local safety regulations appropriate input voltage and the load current...

Page 13: ...14 321 023A 4 R3 17 0 23 0 23 0 15 JJS 35 10 473 027A 4 R6 24 27 27 20 JJS 40 8 625 034A 4 R6 29 34 34 25 JJS 50 8 711 044A 4 R6 34 44 44 30 JJS 60 6 807 052A 4 R6 44 52 52 40 JJS 80 4 960 065A 4 R6...

Page 14: ...ides all other functions of the drive Wiring The safety contacts must open close within 200 ms of each other Double shielded twisted pair cable is recommended for the connection The maximum length of...

Page 15: ...fety function is used for safety component functionality Adjustable speed electrical power drive systems Part 5 2 Safety requirements Functional Safety of machinery Functional safety of safety related...

Reviews: