Table 2: Discharge Time, VLT® HVAC Drive FC 102 and VLT® Refrigeration Drive FC 103

Voltage [V]

Minimum waiting time (minutes)

4

7

15

200–240

1.1–3.7 kW (1.5–5 hp)

5.5–45 kW (7.5–60 hp)

380–480

1.1–7.5 kW (1.5–10 hp)

11–90 kW (15–125 hp)

525–600

1.1–7.5 kW (1.5–10 hp)

11–90 kW (15–125 hp)

525–690

1.1–7.5 kW (1.5–10 hp) (FC 102 only)

11–90 kW (15–125 hp) (FC 102 only)

Table 3: Discharge Time, VLT® AQUA Drive FC 202

Voltage [V]

Minimum waiting time (minutes)

4

7

15

200–240

0.25–3.7 kW (0.34–5 hp)

5.5–45 kW (7.5–60 hp)

380–480

0.37–7.5 kW (0.5–10 hp)

11–90 kW (15–125 hp)

525–600

0.75–7.5 kW (1.0–10 hp)

11–90 kW (15–125 hp)

525–690

1.1–7.5 kW (1.5–10 hp)

11–90 kW (15–125 hp)

Table 4: Discharge Time, VLT® AutomationDrive FC 301/FC 302

Voltage [V]

Minimum waiting time (minutes)

4

7

15

200–240

0.25–3.7 kW (0.34–5 hp)

5.5–37 kW (7.5–50 hp)

380–500

0.25–7.5 kW (0.34–10 hp)

11–75 kW (15–100 hp)

525–600

0.75–7.5 kW (1–10 hp)

11–75 kW (15–100 hp)

525–690

1.5–7.5 kW (2–10 hp)

11–75 kW (15–100 hp)

1.5 Installing the D-Option

Prerequisites:

The following tools are required for installing the option:

Torx 10 screwdriver.

Flat-head screwdriver.

Scope of Delivery, Safety, and Installation

Installation Guide  | VLT® 24 V DC Supply MCB 107

AN287957936346en-000101 / 130R0308 | 3