Parameter
Communication operation and setting
FR-E700 SC EC/ENE
6 - 257
No. Item
Read/
write
Instruction
Code
Data Description
Number
of Data
Digits
(Format)
5
Set frequency (RAM)
Read
H6D
Read set frequency/speed from RAM or
E²PROM.
H0000 to HFFFF: Set frequency in 0.01 Hz incre-
ments
Speed increments 1/0.001 (when Pr. 37 = 0.01
to 9998)
When "0.01 to 9998" is set in Pr. 37 and "01" in
instruction code HFF, the increments change to
0.001 and the data format is E2.
4
(B, E/D)
6
(B, E2/D)
Set frequency (E²PROM)
H6E
Set frequency (RAM)
Write
HED
Write set frequency/speed to RAM or E²PROM.
H0000 to H9C40 (0 to 400.00 Hz):
Frequency increments 0.01 Hz
Speed increments 1/0.001 (when Pr. 37 = 0.01
to 9998)
When "0.01 to 9998" is set in Pr. 37 and "01" in
instruction code HFF, the increments change to
0.001 and the data format is A2.
To change the set frequency consecutively,
write data to the inverter RAM. (instruction
code: HED)
4
(A, C/D)
6
(A2, C/D)
Set frequency
(RAM, E²PROM)
HEE
6 Inverter reset
Write
HFD
H9696: Resets the inverter.
As the inverter is reset at start of communica-
tion by the computer, the inverter cannot send
reply data back to the computer.
4
(A, C/D)
H9966: Resets the inverter.
When data is sent normally, ACK is returned to
the computer and then the inverter is reset.
4
(A, D)
7 Alarm definition all clear
Write
HF4
H9696: Alarm history batch clear
4
(A, C/D)
8 All parameter clear
Write
HFC
All parameters return to the initial values.
Whether to clear communication parameters
or not can be selected according to data.
(
✔
: Clear, —: Not clear) Refer to Tab. 6-1 for
parameter clear, all clear, and communication
parameters.
When all parameter clear is executed for H9696
or H9966, communication-related parameter
settings also return to the initial values. When
resuming operation, set these parameters
again.
Executing clear will clear the instruction code
HEC, HF3, and HFF settings. In the password
locked status only H9966 and H55AA (all
parameter clear) are valid.
4
(A, C/D)
Tab. 6-78:
Setting of the instruction codes and data (2)
Clear Type
Data
Communication Parameter
Parameter clear
H9696
✔
H5A5A
—
All parameter
clear
H9966
✔
H55AA
—
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......