Frequency setting by analog input (terminal 2, 4)
Parameter
6 - 180
Perform operation by analog input voltage
The frequency setting signal inputs 0 to 5 V DC (or 0 to 10 V DC) to across the terminals 2-5. The 5 V
(10 V) input is the maximum output frequency.
The power supply 5 V can be input by either using the internal power supply or preparing an external
power supply. Prepare an external power supply to input the power supply 10 V. For the built-in pow-
er supply, terminals 10-5 provide 5 V DC output.
When inputting 10 V DC to the terminal 2, set "0" or "10" in Pr. 73. (The initial value is 0 to 5 V.)
Setting "1 (0 to 5 V DC)" or "2 (0 to 10 V DC)" in Pr. 267 and a voltage/current input switch in the OFF
position changes the terminal 4 to the voltage input specification. When the AU signal turns on, the
terminal 4 input becomes valid.
Fig. 6-91:
Frequency setting by voltage 0–5 V DC
I001182E
Fig. 6-92:
Frequency setting by voltage 0–10 V DC
I001884E
Terminal
Inverter Built-in
Power Supply Voltage
Frequency Setting
Resolution
Pr. 73 (Terminal 2 Input Voltage)
10
5 V DC
0.1 Hz/50 Hz
0–5 V DC
Tab. 6-47:
Built-in power supply voltage
NOTE
The wiring length of the terminal 10, 2, 5 should be 30 m maximum.
Forward rotation
Frequency
setting
0–5 V DC
Connection diagram
using terminal 2 (0–5 V DC)
PC
Forward rotation
Frequency
setting
0–10 V DC
Connection diagram
using terminal 2 (0–10 V DC)
Voltage input
equipment
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......