55.011
Sauter Components
AXM 117S: Motorised drive (with positioner) for unit valves
How energy efficiency is improved
Automatic valve adjustment and intelligent cut-out enable maximum energy efficiency.
Areas of application
Actuation of through and three-way unit valves in the VUL, BUL, VXL and BXL series. For controllers
with continuous output in combination with intelligent unitary control systems.
Features
•
Pushing force 120 N
•
Fits onto valve with M30 × 1.5 thread
•
Stepping motor with control and electronic cut-off
•
Version with control action A or B or adjustable
•
Maintenance-free gearbox
•
Suitable for retrofitting existing installations using an appropriate adaptor
•
Operating status control using integrated LED display
Technical description
•
Two-part plastic housing, light grey (RAL7035)
•
Nickel-plated brass nut
•
Connecting cable, light grey 1.50 m long, 3 × 0.25 mm²
•
Running time for 4 mm stroke: 60 s
•
Installation position: vertical to horizontal, but not upside down
Operation
During commissioning (with valve fitted), the actuator moves to the two end positions and memorises
the number of steps taken to do so. The 0...10 V control signal is then linearly assigned to this effec-
tive stroke. The motor activates the valve and switches off as soon as the stroke position concurs with
the controller signal. In the end positions or in the event of an overload, the motor is switched off with-
in 2 minutes. If the control voltage has not changed for 2 hours (in the range 0...0,5 V), the motor –
after approx. 2 hours – runs briefly to the end positions and, if necessary, corrects its position
memory. A complete cycle is performed every 24 hours on the AXM117SF202 and F302 in order to
prevent the plug from jamming. The LED lights up when power is applied to the drive, and flashes
when the motor is running.
Y07552
M
100 %
0 V Output signal y 10 V
B07650
0 %
Direc
tion
of op
era
tion 2
Dir
ec
tio
n
of op
era
tion 1
Type
Direction of
operation
1)
Running
time
Stroke
Thrust
Power
Weight
s
mm
N
kg
AXM 117S F202
1
60
4
120
2)
24 V~
0,15
AXM 117S F302
2
60
4
120
2)
24 V~
0,15
AXM 117S F402
1 or 2
3)
60
4
120
2)
24 V~
0,15
Power supply 24 V~
±
15%, 50...60 Hz
Ambient temperature
–0...50 °C
Power consumption on
starting
5 VA
Ambient humidity
< 75% rh
Type of protection
IP 40 (EN 60529)
Control voltage
0...10 V; Ri = 20 k
Ω
Protection class
III (IEC 60730)
Control voltage F402
3)
0...10 V; 5,2...10 V; 0...4,8 V
Wiring diagram
Control current
max. 0,5 mA
Dimension drawing
Max. operating temperature 100 °C at valve
Fitting instructions
MV 505456
Accessories
0371235 001
Adaptor for fitting to
Oventrop
valves (M30
×
1)
0550393 001
Adaptor Danfoss RA2000, 22 mm
0371356 001
Adaptor for fitting to
Beulco
or
Tobler
underfloor-heating distribution stations (M30
×
1)
0550393 002
Adaptor Danfoss RAVL, 26 mm
0550393 003
Adaptor Danfoss RAV, 34 mm
0371361 001
Adaptor for fitting to
Herz
valves, type Herz-TS’90 (M28
×
1,5)
0371363 001
Adaptor for fitting to
Tour
& Andersson
valves, type TA/RVT (M28
×
1,5)
1)
Direction of operation 1: rising 0…10V = drive retracts (VXL, VUL, BUL opens, BXL control passage closes).
Direction of operation 2: rising 0…10V = drive extends (VXL, VUL, BUL closes, BXL control passage opens).
2)
Pushing force: min. 100 N, max. 150 N
3)
The direction of operation and the setting of the control voltage can be set using jumpers
7155011003 07