CC-Link IE Field Network Basic
Parameter
6 - 360
– Reply code definition
The reply to the instruction execution is set to RWr2, 10, 12, 14, 16, 18.
When executing the frequency setting (RYD, RYE) or instruction code execution (RYF), check the
reply code (RWr2) in the remote register after execution.
Data
Item
Alarm definition
Remarks
Reply code
H0000
Normal
No error (normal completion of instruc-
tion code execution)
앫
Reply code to RWr2
when Pr. 544 = 0
앫
Reply code to RWw10,
12, 14, 16, and 18 when
Pr. 544 = 18
H0001
Write mode error
Parameter write was attempted during
operation other than a stop in the net-
work operation mode.
H0002
Parameter selection
error
Unregistered code number was set.
H0003
Setting range error
Set data is outside the permissible data
range.
Reply code 1
H00
Normal
No error (normal completion of instruc-
tion code execution)
Reply code to RWr2 when
Pr. 544 0
H01
Write mode error
Parameter write was attempted during
operation other than a stop in the net-
work operation mode.
H03
Frequency command
setting range error
The value outside the range is set.
Reply code 2
H00
Normal
No error (normal completion of instruc-
tion code execution)
H01
Write mode error
Parameter write was attempted during
operation other than a stop in the net-
work operation mode.
H02
Parameter selection
error
Unregistered code number was set.
H03
Setting range error
Set data is outside the permissible data
range.
Tab. 6-160:
Reply codes
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......