Setting for the parameter unit, operation panel
Parameter
6 - 330
6.22.3
Operation panel frequency setting/key lock operation selection (Pr. 161)
The setting dial of the operation panel can be used like a potentiometer to perform operation. The key
operation of the operation panel can be disabled.
The above parameter can be set when Pr. 160 "User group read selection" = 0.
Pr. No.
Name
Initial Value
Setting
Range
Description
Parameters referred to
Refer to
Section
161
Frequency setting/key lock
operation selection
0
0
Setting dial
frequency setting
mode
Key lock mode invalid
—
1
Setting dial
potentiometer
mode
10
Setting dial
frequency setting
mode
Key lock mode valid
These setting must be
confirmed by pressing the
MODE key for about 2s.
11
Setting dial
potentiometer
mode
NOTES
You can find a detailed description of the operation panel with examples in section 4.3 "Operation
Panel".
When the setting dial and key operation is made invalid, "HOLD" appears on the operation panel
while pressing a key.
The STOP/RESET key is valid even in the operation lock status.