Description

The in-back/out-back cooling kit is designed for the specific

VLT

®

 HVAC Drive FC 102, VLT

®

 AQUA Drive FC 202, and VLT

®

AutomationDrive FC 302 D4h-size VLT

®

 Parallel Drive Modules

mounted in a Rittal TS8 enclosure. The kit directs air in from
and out of the back of the unit. See 

Illustration 1.1

.

1

Top plate assembly

2

Base duct assembly

3

Mounting backplate

4

Back-channel airflow

Illustration 1.1 Direction of Airflow with the Kit Installed

Kit Part Number

Part number

Kit description

176F6493

In-back/Out-back Cooling Kit for the VLT

®

 Parallel

Drive Modules (2-drive system)

Table 1.1 Part Number for the VLT

®

 Parallel Drive Modules

In-back/Out-back Cooling Kit

Items Supplied

Top plate assembly

Top cover (1)

Gasket, top cover (1)

Gasket, cut out (1)

Screws, M5x12 (11)

Enclosure mounting assembly

Base mounting plate, 38 mm (1.5 in.) (2)

Gasket, base mounting plate (2)

Gasket, frequency converter exhaust vent (1)

Screws, M5x12 (11)

Nuts, M10 (4)

Gasket, enclosure exhaust vent (1)

Gasket, enclosure intake vent (1)

Torx screws, M5x12 (14)

Installation Instructions

In-back/Out-back Cooling Kit for VLT®
Parallel Drive Modules
VLT® Series FC 102, FC 202, and FC 302

Danfoss A/S © 04/2016 All rights reserved.

MI92J102

Summary of Contents for 176F6493

Page 1: ...on 176F6493 In back Out back Cooling Kit for the VLT Parallel Drive Modules 2 drive system Table 1 1 Part Number for the VLT Parallel Drive Modules In back Out back Cooling Kit Items Supplied Top plate assembly Top cover 1 Gasket top cover 1 Gasket cut out 1 Screws M5x12 11 Enclosure mounting assembly Base mounting plate 38 mm 1 5 in 2 Gasket base mounting plate 2 Gasket frequency converter exhaus...

Page 2: ...g battery back ups UPS and DC link connections to other frequency converters Wait 20 minutes for the capacitors to discharge fully before performing any service or repair work Measure the voltage level to verify full discharge Installation NOTICE If both a bus bar kit and a back channel cooling kit are being installed in the cabinet install the back channel cooling kit first NOTICE APPROVALS AND C...

Page 3: ...ll the 12 screw holes around the exhaust top vent openings and insert the 12 M5 X 12 pem studs 3 Drill the 12 screw holes around the intake bottom vent openings and insert the 12 M5 X 12 pem studs Illustration 1 3 Vent Dimensions for Mounting Plate Installation Instructions In back Out back Cooling Kit for VLT Parallel Drive Modules VLT Series FC 102 FC 202 and FC 302 MI92J102 Danfoss A S 04 2016 ...

Page 4: ...1 Nm 45 in lb 6 Install the gasket 1 on the top plate Leave the paper backing on the adhesive until ready to install on the drive module 7 Turn the duct enclosure over so the base of the enclosure is facing up Install the top side gaskets 4 on the sides of the top plate 2 8 Place a top side cover 5 on each gasket 4 Secure each cover with 5 M5 nuts and torque to 5 1 Nm 45 in lb Illustration 1 4 Ass...

Page 5: ...screws are secure since the base of the drive module rests on these screws 4 Slightly lean the top of the drive module forward and set the cutouts in the base of the module onto the lower 2 M10 screws in the mounting backplate 5 Slowly push the top of the drive module back against the mounting backplate until the top 2 holes on the module line up with the 2 mounting holes in the mounting backplate...

Page 6: ...slot 3 Gasket between drive module exhaust and mounting backplate Illustration 1 5 Installing the Drive Modules to the Mounting Back Plate Installation Instructions In back Out back Cooling Kit for VLT Parallel Drive Modules VLT Series FC 102 FC 202 and FC 302 6 Danfoss A S 04 2016 All rights reserved MI92J102 ...

Page 7: ...m 45 in lb 5 On the front side of the lower duct install the front cover gasket 10 and then the front cover plate 9 Refer to Illustration 1 4 Secure with 8 M5 nuts and torque to 5 1 Nm 45 in lb 6 Install the lower duct assembly for the next drive module 1 Drive module 5 Base mounting plate 38 mm 1 5 in 2 Gasket slot 6 M10 screw 3 Cutout in drive module base that rests on the M10 screw 7 M5x16 scre...

Page 8: ...n lb 5 Place a gasket 3 onto each exhaust duct spacer 6 Place a gasket 7 onto each intake duct spacer 7 Prepare the back panel cover Refer to Illustration 1 8 7a Cut out the 2 intake and 2 exhaust vent openings in the back panel The openings must match to the intake and exhaust duct spacer openings 7b Drill the 16 screw holes around the vent openings 8 Secure the back panel cover to the frame 9 Se...

Page 9: ...pacer intake 3 Gasket between the exhaust duct spacer and the back panel 7 Gasket between the intake duct spacer and the back panel 4 Mounting plate Illustration 1 7 Installing the Duct Spacers Installation Instructions In back Out back Cooling Kit for VLT Parallel Drive Modules VLT Series FC 102 FC 202 and FC 302 MI92J102 Danfoss A S 04 2016 All rights reserved 9 ...

Page 10: ...ce This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respective companies Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved Danfoss A S Ulsnaes 1 DK 6300 Graasten vlt drives danfoss com MI92J102 M...

Reviews: