APPLICATIONS:

  

This emergency driver can be used with most LED loads that have 
a  rated  voltage  of  25-48Vdc. These  emergency  packs have been 
evaluated to and found compliant to UL 924. The emergency pack 
assembly  is  accepted  as  a  component  of  a  luminaire  where  the 
suitability  of  the  combination  shall  be  determined  by  UL  or 
authorities having jurisdiction. The as-installed performance of the 
system  must  meet  or  exceed  all  Federal,  State  and  local  code 
requirements. 

 

FEATURES: 

 

Selectable emergency power 10W, 15W and 20W 

 

Constant  output  power  (auto-sensing  output  within 
each range) 

 

Output class 2 complaint 

 

Battery protection: over voltage protection, low voltage 
protection,  over  temperature  protection  and  short 
circuit protection 

 

 

DIMENSIONS: 

OPERATION:

  

AC Operation:

 AC power is present. The AC driver operates the lED 

load  (the  LED  load  must  be  less  than  100W)  as  designed.  The 
emergency pack is charging in a standby mode. The test button will 
be lit showing that the battery is charging.  

Emergency  operation:

  When  the  AC  power  goes  out,  the 

emergency  pack  detracts  the  power  outage  and  automatically 
switches to the emergency mode. The LED load is illuminated for a 
minimum  of  90  minutes.  When  the  AC  power  is  restored,  the 
emergency  pack  switches  back  to  normal  mode  and  starts  re-
charging. 

Testing Procedures: 

Press the test button to cut the power to the 

AC driver and switch the system to emergency mode. Release the 
test button to return to normal mode. Switch off the circuit 
breaker to simulate a full power outage. For initial testing, allow 
the unit to charge approximately 1 hour. Then conduct a short 
discharge test. Allow a 24-hour charge before conducting a 1-hour 
test. 

NFPA 101 Life Safety Code outlines the following schedule: 

Monthly 

 Ensure that the test button light is illuminated. Conduct 

a 30 second discharge test by depressing the test button. The LED 
load should operate at reduced output. 

Annually 

 Ensure that the test button is illuminated. Conduct a 

full 90-minute discharge test. The unit should operate as intended 
for the duration of the test.

 

 

 

 

 

 

 

 