INSTALLATION AND OPERATION MANUAL 

ASD SERIES 

 

Adjustable Frequency Drive for 3-Phase AC Motors 

NEMA 4X / IP65 

 

Variable Speed / Soft-Start AC Motor Drive 

With Electronic Motor Overload Protection

1

 

 Washdown and Watertight for Indoor and Outdoor Use 

 

Rated for 208 

– 230 and 400/460 Volt 50 Hz and 60 Hz 

3-Phase and PSC

2

 AC Induction Motors from Subfractional thru 10 HP 

 

Operates from 115, 208/230, and 400/460 Volt 50/60 Hz AC Line Input 

 

 

 

NOTE: 

The  drive  is  factory  set  for 

60 Hz motors. For 50 Hz motors, see 
Section 10.4 on page 15.

 

 

See Safety Warnings on page 5.

 

 

LISTED 

IND. CONT. 
EQ. 

– 70ZA 

 

RoHS

 

 

This Manual Covers Models 

ASD-24D, 27D, 29, 29 (1P), 45, 48 

 

The information contained in this manual is intended to be accurate.  

However, the manufacturer retains the right to make changes in design which may not be included herein. 

 

Notes: 1. UL approved as an electronic overload protector for motors. 2. Special software is available for PSC motors 

– contact 

Technical Support. 3. Installation of a CE approved RFI (EMI) filter is required.

 

 

 

Copyright © 2019 
Acme Engineering & Mfg. Corp. 

(See Back Cover) 

 

 

 

Summary of Contents for ACME SYNC ASD Series

Page 1: ...TE The drive is factory set for 60 Hz motors For 50 Hz motors see Section 10 4 on page 15 See Safety Warnings on page 5 LISTED IND CONT EQ 70ZA 3 RoHS This Manual Covers Models ASD 24D 27D 29 29 1P 45...

Page 2: ...Hz Motor Operation 15 10 4 2 Setting the Drive for Two Times the Rated Motor RPM 15 10 5 Boost Mode Selection J6 16 10 6 Braking Mode Selection J7 16 10 7 Run Fault Output Relay Operation Selection J...

Page 3: ...oost Mode Selection J6 16 19 Braking Mode Selection J7 16 20 Run Fault Output Relay Operation Selection J8 16 21 Stop Contact Type Selection J9 16 22 Torque Mode Selection J10 16 23 Switching Frequenc...

Page 4: ...lt AC Line input and 2 HP maximum with 208 230 Volt AC Line input ASD 29 Designed to accept 1 phase Terminals L1 L2 or 3 phase Terminals L1 L2 L3 AC Line input Rated for 208 230 Volt AC Line input onl...

Page 5: ...tilated 3 phase AC induction motors will overheat if used beyond a limited speed range at full torque Therefore it is necessary to reduce motor load as speed is decreased Note Some fan cooled motors c...

Page 6: ...rial Duty Die Cast Aluminum Case with Hinged Cover Available in dark gray finish or FDA approved white finish Simple to Operate Does not require programming Uses trimpots and jumpers which are factory...

Page 7: ...put Voltage Operating Range Volts AC 208 15 230 15 400 460 Volt AC Line Input Voltage Operating Range Volts AC 380 15 460 15 Maximum Load Current Overload for 2 Minutes 150 Switching Frequency kHz Jum...

Page 8: ...on See Section 10 2 on page 15 5 Jumper J5 Motor Frequency selection See Section 10 4 on page 19 6 Jumper J12 Switching Frequency and GFCI selection See Section 10 11 on page 16 7 Jumper J6 Adjustable...

Page 9: ...ee Section 10 5 on page 16 5 Jumper J4 Frequency Multiplier selection See Section 10 4 on page 15 6 Jumper J7 Regeneration or DC Injection Braking See Section 10 6 on page 16 7 Jumper J5 Motor Frequen...

Page 10: ...15 4 Jumper J6 Adjustable Boost selection See Section 10 5 on page 16 5 Jumper J4 Frequency Multiplier selection See Section 10 4 on page 15 6 Jumper J7 Regeneration or DC Injection Braking See Sectio...

Page 11: ...should be taken to avoid extreme hazardous locations where physical damage can occur When mounting the drive in an enclosure the enclosure should be large enough to allow for proper heat dissipation s...

Page 12: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 12 FIGURE 8 ASD 27D 29 29 1P 45 48 MECHANICAL SPECIFICATIONS Inches mm Tighten these screws in the sequence shown to 12 in lbs 14 kg cm...

Page 13: ...gasket is slightly compressed The recommended tightening torque is 12 in lbs 14 kg cm do not overtighten See Figures 7 and 8 on pages 11 and 12 for the tightening sequence Application Note To avoid e...

Page 14: ...G All equipment AC Line inputs must be disconnected from the AC power Connect all equipment AC power input lines together and connect them to the H V lead of the hi pot tester Connect the RETURN lead...

Page 15: ...ut 10 3 AUTOMATIC RIDE THROUGH OR MANUAL START SELECTION J3 Jumper J3 is factory set to the A or AUTO position for Automatic Ride Through If the power is interrupted for up to 2 seconds the drive will...

Page 16: ...ing Frequency 8 kHz Switching Frequency Factory setting 11 DRIVE OPERATION 11 1 START UP PROCEDURE After the drive has been properly setup jumpers and trimpots set to the desired positions and wiring...

Page 17: ...generation Protection It is recommended that for very high inertial loads that both the ACCEL and DECEL Trimpots be set to greater than 10 seconds 12 5 DC INJECTION BRAKE TRIMPOT DECEL The drive is fa...

Page 18: ...which provides indication of a fault or abnormal condition The information provided can be used to diagnose an installation problem such as incorrect input voltage overload condition and drive output...

Page 19: ...ge Volts DC 0 to 2 5 thru 0 to 25 0 to 5 Signal Offset Trimpot OFFSET Range of SCALE Trimpot Setting 0 40 0 Input Current Range mA DC 4 20 Forward and Reverse Input Switch Types Dry Contact or Open Co...

Page 20: ...ve for a specific application 14 2 1 SCALE TRIMPOT SCALE The SCALE Trimpot is factory set to run the motor at full speed with a 10 Volt DC analog signal input For a higher analog signal input 25 Volt...

Page 21: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 21 NOTES...

Page 22: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 22 NOTES...

Page 23: ...ASD SERIES INSTALLATION AND OPERATION MANUAL 23 NOTES...

Page 24: ...uding injury to any person caused by items of our manufacture or sale Some states do not allow certain exclusions or limitations found in this warranty and therefore they may not apply to you In any e...

Reviews: