VLT® 4000 VT
Installation
■
General technical data
Line supply (L1, L2, L3):
Supply voltage 200-240 V units ........................................................................ 3 x 200/208/220/230/240 V ±10%
Supply voltage 380-460 V units ........................................................................ 3 x 380/400/415/440/460 V ±10%
Supply voltage 525-600 V units ............................................................................... 3 x 525/550/575/600 V ±10%
Supply frequency ......................................................................................................................... 48-62 Hz +/- 1%
Max. imbalance of supply voltage:
VLT 4006 - 4011 VT / 380 - 460 V and 525 - 600 V ................................................
±2.0% of rated supply voltage
VLT 4016 - 4062 VT / 380 - 460 V and VLT 4006 - 4032 VT / 200 - 240 V .............. ±1.5% of rated supply voltage
VLT 4016 - 4072 VT / 525 - 600 V ........................................................................... ±1.5% of rated supply voltage
VLT 4072 - 4600 VT / 380 - 460 V and VLT 4042 - 4062 VT / 200 - 240 V .............. ±3.0% of rated supply voltage
VLT 4100 - 4300 VT / 525 - 600 V ........................................................................... ±3.0% of rated supply voltage
Power factor / cos.
ϕ
............................................................................................................ 0.90/1.0 at rated load
No. of switches on supply input L1, L2, L3 ........................................................................... approx. 1 time/2 min.
Max. short-circuit current ....................................................................................................................... 100.000 A
VLT output data (U, V, W):
Output voltage ................................................................................................................ 0-100% of supply voltage
Output frequency:
Output frequency 4006-4032, 200-240V .............................................................................. 0-120 Hz, 0-1000 Hz
Output frequency 4042-4062, 200-240V ................................................................................ 0-120 Hz, 0-450 Hz
Output frequency 4006-4062, 380-460V .............................................................................. 0-120 Hz, 0-1000 Hz
Output frequency 4072-4122, 380-460V ................................................................................ 0-120 Hz, 0-450 Hz
Output frequency 4152-4352, 380-460V ................................................................................ 0-120 Hz, 0-800 Hz
Output frequency 4450-4600, 380-460V ................................................................................ 0-120 Hz, 0-450 Hz
Output frequency 4006-4016, 525-600V .............................................................................. 0-120 Hz, 0-1000 Hz
Output frequency 4022-4062, 525-600V ................................................................................ 0-120 Hz, 0-450 Hz
Output frequency 4072-4300, 525-600V ................................................................................ 0-120 Hz, 0-450 Hz
Rated motor voltage, 200-240 V units .............................................................................. 200/208/220/230/240 V
Rated motor voltage, 380-460 V units .............................................................................. 380/400/415/440/460 V
Rated motor voltage, 525-600 V units ............................................................................................ 525/550/575 V
Rated motor frequency ............................................................................................................................ 50/60 Hz
Switching on output ................................................................................................................................. Unlimited
Ramp times ....................................................................................................................................... 1 - 3600 sec.
Torque characteristics:
Starting torque ............................................................................................................................... 110% for 1 min.
Starting torque (parameter 110
High break-away torque
) ....................................... Max. torque: 130% for 0.5 sec.
Acceleration torque ....................................................................................................................................... 100%
Overload torque ............................................................................................................................................ 110%
Control card, digital inputs:
Number of programmable digital inputs ................................................................................................................ 8
Terminal nos. ............................................................................................................ 16, 17, 18, 19, 27, 29, 32, 33
Voltage level ........................................................................................................... 0-24 V DC (PNP positive logics)
Voltage level, logical "0" ........................................................................................................................... < 5 V DC
Voltage level, logical "1" ......................................................................................................................... > 10 V DC
MG.40.A4.22 - VLT is a registered Danfoss trademark
13