VLT® 4000 VT
525-600 V
Bussmann
SIBA
Littel fuse
Ferraz-Shawmut
4006
KTS-R8
5017906-008
KLS-R008
A6K-8R
4008
KTS-R10
5017906-010
KLS-R010
A6K-10R
4011
KTS-R15
5017906-016
KLS-R015
A6K-15R
4016
KTS-R20
5017906-020
KLS-R020
A6K-20R
4022
KTS-R30
5017906-030
KLS-R030
A6K-30R
4027
KTS-R35
5014006-040
KLS-R035
A6K-35R
4032
KTS-R45
5014006-050
KLS-R045
A6K-45R
4042
KTS-R60
5014006-063
KLS-R060
A6K-60R
4052
KTS-R75
5014006-080
KLS-R075
A6K-80R
4062
KTS-R90
5014006-100
KLS-R090
A6K-90R
4072
KTS-R100
5014006-100
KLS-R100
A6K-100R
4100
FWP-125A
2018920-125
L70S-125
A70QS-125
4125
FWP-175A
2018920-180
L70S-175
A70QS-175
4150
FWP-200A
2018920-200
L70S-200
A70QS-200
4200
FWP-250A
2018920-250
L70S-250
A70QS-250
4250
FWP-350A
206XX32-350
L70S-350
A70QS-350
4300
FWP-400A
206xx32-400
L70S-400
A70QS-400
KTS-fuses from Bussmann may substitute KTN for 240 V drives.
FWH-fuses from Bussmann may substitute FWX for 240 V drives.
KLSR fuses from LITTEL FUSE may substitute KLNR fuses for 240 V drives.
L50S fuses from LITTEL FUSE may substitute L50S fuses for 240 V drives.
A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V drives.
A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V drives.
Non UL compliance
If UL/cUL is not to be complied with, we recommend the above mentioned fuses or:
VLT 4006-4032
200-240 V
type gG
VLT 4042-4062
200-240 V
type gR
VLT 4006-4072
380-460 V
type gG
VLT 4102-4600
380-460 V
type gR
VLT 4006-4072
525-600 V
type gG
VLT 4100-4300
525-600 V
type gR
Not following the recommendation may result
in unnecessary damage of the drive in case of
malfunction. Fuses must be designed for protection in
a circuit capable of supplying a maximum of 100000
A
rms
(symmetrical), 500 V/600 V maximum.