VLT® 4000 VT
■
Line Supply, 3 x 525 - 600 V
Output
VLT type
4
4016
4022
4027
4032
4042
4052
4062
4072
Output Current
I
VLT,N
[A] (550 V)
18
23
28
34
43
54
65
81
I
VLT, MAX
(60 s) [A] (550 V)
20
25
31
37
47
59
72
89
I
VLT, N
[A] (575 V)
17
22
27
32
41
52
62
77
I
VLT, MAX
(60 s) [A] (575 V)
19
24
30
35
45
57
68
85
Output
S
VLT,N
[kVA] (550 V)
17
22
27
32
41
51
62
77
S
VLT,N
[kVA] (575 V)
17
22
27
32
41
52
62
77
Typical shaft output
P
VLT,N
[kW]
11
15
18.5
22
30
37
45
55
Typical shaft output
P
VLT,N
[HP]
15
20
25
30
40
50
60
75
Max. copper cable
cross-section to motor
and loadsharing
4)
[mm
2
/AWG]
2)
16
6
16
6
16
6
35
2
35
2
50
1/0
50
1/0
50
1/0
Min. cable cross-section
to motor
and loadsharing
3)
[mm
2
/AWG]
2)
0.5
20
0.5
20
0.5
20
10
8
10
8
16
6
16
6
16
6
Input
Rated Input Current
I
VLT,N
[A] (550 V)
18
22
27
33
42
53
63
79
I
VLT, N
[A] (600 V)
16
21
25
30
38
49
58
72
Max. copper cable
cross-section power,
NEMA 1
4)
[mm
2
/AWG]
2)
16
6
16
6
16
6
35
2
35
2
50
1/0
50
1/0
50
1/0
Max. pre-fuses (mains)
1)
[-]/UL
1)
[A]
20
30
35
45
60
75
90
100
Efficiency
0.96
Weight IP20 / NEMA 1
[kg]
23
23
23
30
30
48
48
48
[lbs]
51
51
51
66
66
106
106
106
Estimated power loss at
max. load
[W]
451
576
707
852
1077
1362
1628
2029
Enclosure
NEMA 1
1. See section
Fuses.
2. American Wire Gauge (AWG).
3. Min. cable cross-section is the smallest cable cross-section allowed to be fitted into the terminals to comply with IP 20. Always comply with national and
local regulations on min. cable cross-section.
4. Aluminum cables with cross section above 35 mm
2
/AWG 2 must be connected by use of an Al-Cu connector.