VLT® 4000 VT
■
Motor connection
The motor must be connected to terminals 96,
97, 98. Ground to terminal 99.
Nos. 96, 97, 98
Motor voltage 0-100% of
U, V, W
line voltage.
No. 99
Ground connection.
See
Technical data
for correct sizing of cable
cross-sections.
All types of three-phase asynchronous standard
motors can be used with a VLT 4000 VT unit.
Small-size motors are normally star-connected.
(220/380 V,
/Y).
Large-size motors are delta-connected (380/660
V,
/Y). The correct connection and voltage can
be read from the motor nameplate.
NOTE
In older motors without phase coil insulation, a
LC filter should be fitted to the VLT AFD output.
See the Design Guide or contact Danfoss.