Communication operation and setting
Parameter
6 - 292
6.19.8
USB communication (Pr. 547, Pr. 548)
Inverter setup can be easily performed using the FR Configurator by connecting the inverter and per-
sonal computer with a USB cable. A personal computer and inverter can be easily connected with one
USB cable.
햲
Changed setting value is made valid when powering on or resetting the inverter.
You can perform parameter setting and monitoring with the FR Configurator. Refer to the instruction
manual of the FR Configurator for details.
Pr. No.
Name
Initial Value
Setting Range Description
Parameters referred to
Refer to
Section
547
USB communication station
number
햲
0
0–31
Inverter station number specification
551 PU mode operation
command source selection
548
USB communication check
time interval
햲
9999
0
USB communication is possible
Trips in the PU operation mode (E.USB)
0.1–999.8 s
Sets the interval of communication check time. If a
no-communication state persists for longer than
the permissible time, the inverter will come to trip
(E.USB).
9999
No communication check
Specification
Description
Interface
Conforms to USB1.1
Transmission speed
12 Mbps
Wiring Length
5 m
Connector
USB mini B connector (receptacle mini B type)
Power supply
Self-power supply
Tab. 6-111:
USB communication specifications
I001921E
Fig. 6-145:
Connection to the USB connector
USB cable
USB connector
How to open the USB connector cover
Pull the cover in the direction of arrow.
Then turn it upward.
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......