6 - 33
MELSEC-A
6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL
6.5.5 Restart program
When a stop factor occurs during position control and the operation stops, the
positioning can be restarted from the stopped position to the position control end point
by using the "restart command" ( Cd.13 Restart command).
("Restarting" is not possible when "continuous operation is interrupted.")
(1) Restart operation
Axis 2
Axis 1
Stop with stop command
Positioning data No. 11
continues with restart
command
Positioning with positioning data No. 11
Positioning with positioning data No. 10
Positioning with positioning data No. 12
Fig. 6.12 Restart operation
(2) Restrictions
(1) Restarting can be executed only when the " Md.35 Axis operation status" is
"stopped".
If the axis operation is not "stopped", restarting is not possible.
(2) Do not execute restart while the stop command is ON.
If restart is executed while stopped, an error "Stop signal ON at start" (error
code:106) will occur, and the " Md.35 Axis operation status" will change to
"error occurring".
Thus, even if the error is reset, the operation cannot be restarted.
(3) Restarting can be executed even while the positioning start signal is ON.
However, make sure that the positioning start signal does not change from
OFF to ON while stopped.
If the positioning start signal changes from OFF to ON, positioning will start
from the positioning data No. of designated point's positioning data No. set in
" Cd.11 Positioning start No.".
(4) If positioning is ended with the continuous operation interrupt request, the
operation cannot be restarted.
If restart is requested, a warning "Restart not possible" (warning code:104) will
occur.
(5) When stopped with interpolation operation, write "1: restarts" into " Cd.13
Restart command" for the reference axis, and then restart.
(6) If the " Md.35 Axis operation status" is not "stopped" when restarting, a
multiple start warning will occur, and the process at that time will be continued.
REMARK
Restarting after stopping is possible even for the following control.
•
Incremental type position control
•
Continuous positioning control
•
Continuous path control
•
Block start
Summary of Contents for A1SD75M1
Page 2: ......
Page 20: ...A 18 MEMO...
Page 22: ...MEMO...
Page 27: ...1 5 MELSEC A 1 PRODUCT OUTLINE MEMO...
Page 42: ...1 20 MELSEC A 1 PRODUCT OUTLINE MEMO...
Page 52: ...2 10 MELSEC A 2 SYSTEM CONFIGURATION MEMO...
Page 111: ...5 21 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 115: ...5 25 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 123: ...5 33 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 127: ...5 37 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 167: ...5 77 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 193: ...5 103 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 276: ...5 186 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 332: ...7 18 MELSEC A 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO...
Page 334: ...MEMO...
Page 422: ...9 64 MELSEC A 9 MAIN POSITIONING CONTROL MEMO...
Page 446: ...10 24 MELSEC A 10 ADVANCED POSITIONING CONTROL MEMO...
Page 472: ...11 26 MELSEC A 11 MANUAL CONTROL MEMO...
Page 576: ...12 104 MELSEC A 12 CONTROL AUXILIARY FUNCTIONS MEMO...
Page 745: ......