14 - 2
MELSEC-A
14 TROUBLESHOOTING
14.1 Error and warning details
(1) Errors
Types of errors
Errors include AD75-detected parameter setting range errors and errors at
operation start/during operation, and servo amplifier-detected errors.
(1) Parameter setting range errors detected by AD75
The parameters are checked when the power is turned ON and at the rising
edge (OFF ON) of the PLC READY signal [Y1D]. An error will occur if there
is a mistake in the parameter setting details at that time.
When this kind of error occurs, the AD75 READY signal does not turn OFF.
To cancel this kind of error, set the correct value in the parameter for which
the error occurred, and then turn ON the PLC READY signal [Y1D].
POINT
If the AD75 does not start up due to occurrence of many errors 900 to 997, initialize
the parameters (refer to section 13.2) and then set them again.
(2) Errors detected by AD75 at operation start/during operation
These are errors that occur at the operation start or during operation when
using positioning control, JOG operation, manual pulse generator operation,
etc. If an axis error occurs during interpolation operation, the error No. will be
stored in both the reference axis and the interpolation axis.
Note that in the following cases (a) and (b), the axis error No. will only be
stored in the reference axis during analysis of the positioning data set in each
point of the positioning start data table.
(a) When the interpolation axis is BUSY
(b) When the error occurred in positioning data or parameters unrelated to
interpolation control.
If the error occurred at the simultaneous start of a positioning operation, the
axis error storage details will differ depending on whether the error occurred
before or after the simultaneous start.
•
If the error occurred before the simultaneous start (illegal axis No., other axis
BUSY, etc.), an "error before simultaneous start" will occur.
•
If the error occurred after the simultaneous start (positioning data error,
software stroke limit error, etc.), an error code corresponding to the axis in
which the error occurred will be stored. Because a simultaneous start cannot
be carried out due to this, a "simultaneous start not possible error" error code
will be stored in all axes in which an error has not occurred.
The axis operation status will be displayed as "error occurring" for axes in
which an error occurred.
If an error occurs during operation, any moving axes will deceleration stop,
and their operation status will be displayed as "error occurring".
Both axes will decelerate to a stop during interpolation operations, even if the
error occurs in only one axis.
(3) Errors detected by servo amplifier
These are errors that occur due to a hardware fault of the servo amplifier,
servomotor, etc. or due to a servo parameter error.
At error occurrence, the servo switches OFF and the axis stops.
After removing the error factor, reset the servo amplifier.
Summary of Contents for A1SD75M1
Page 2: ......
Page 20: ...A 18 MEMO...
Page 22: ...MEMO...
Page 27: ...1 5 MELSEC A 1 PRODUCT OUTLINE MEMO...
Page 42: ...1 20 MELSEC A 1 PRODUCT OUTLINE MEMO...
Page 52: ...2 10 MELSEC A 2 SYSTEM CONFIGURATION MEMO...
Page 111: ...5 21 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 115: ...5 25 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 123: ...5 33 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 127: ...5 37 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 167: ...5 77 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 193: ...5 103 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 276: ...5 186 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 332: ...7 18 MELSEC A 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO...
Page 334: ...MEMO...
Page 422: ...9 64 MELSEC A 9 MAIN POSITIONING CONTROL MEMO...
Page 446: ...10 24 MELSEC A 10 ADVANCED POSITIONING CONTROL MEMO...
Page 472: ...11 26 MELSEC A 11 MANUAL CONTROL MEMO...
Page 576: ...12 104 MELSEC A 12 CONTROL AUXILIARY FUNCTIONS MEMO...
Page 745: ......