8 - 21
MELSEC-A
8 ZERO POINT RETURN CONTROL
8.4 Positioning to the zero point
Positioning to the zero point is explained in this section.
To carry out positioning to the zero point, "1-axis linear control (ABS) positioning data"
is created in which the " Md.43 Zero point absolute position" is set in the positioning
address ( Da.5 ). In this case, the other positioning data items are set beforehand in
the flash ROM. (This control is called a "high-speed machine zero point return".)
Restrictions
The "zero point absolute position overflow/underflow flags" ( Md.40 Status:
b11/b12) must be turned OFF.
Positioning data setting example
The following table shows setting examples in which "zero point positioning" is set
in the positioning data No. 100 of axis 1.
Setting item
Setting
example
Setting details
Da.1
Operation pattern
Positioning
complete
Set "Positioning complete" so the next positioning data is not executed.
Da.2
Control method
ABS linear 1 Set the absolute system 1-axis linear control.
Da.3
Acceleration time No.
0
Designate the value set in "
Pr.8 Acceleration time 0" as the
acceleration time at start.
Da.4
Deceleration time No.
0
Designate the value set in "
Pr.9 Deceleration time 0" as the
deceleration time at deceleration.
Da.5
Positioning address/
movement amount
Set "
Md.43 Zero point absolute position" in the positioning address.
(Assuming that the "
Pr.1 Unit setting" is set to "mm".)
Da.6
Arc address
–
Setting not required. (Setting value will be ignored.)
Da.7
Command speed
20.00mm/min Set the speed when moving to the positioning address.
Da.8
Dwell time
500ms
Set the time from the positioning stop (position command output stop)
to the output of the positioning complete signal.
Ax
is 1 Positioning data N
o
. 1
Da.9
M code
0
Set when carrying out other auxiliary operation commands in
combination with the No. 1 positioning data
* Refer to section "5.3 List of positioning data" for information on the setting details.
Summary of Contents for A1SD75M1
Page 2: ......
Page 20: ...A 18 MEMO...
Page 22: ...MEMO...
Page 27: ...1 5 MELSEC A 1 PRODUCT OUTLINE MEMO...
Page 42: ...1 20 MELSEC A 1 PRODUCT OUTLINE MEMO...
Page 52: ...2 10 MELSEC A 2 SYSTEM CONFIGURATION MEMO...
Page 111: ...5 21 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 115: ...5 25 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 123: ...5 33 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 127: ...5 37 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 167: ...5 77 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 193: ...5 103 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 276: ...5 186 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 332: ...7 18 MELSEC A 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO...
Page 334: ...MEMO...
Page 422: ...9 64 MELSEC A 9 MAIN POSITIONING CONTROL MEMO...
Page 446: ...10 24 MELSEC A 10 ADVANCED POSITIONING CONTROL MEMO...
Page 472: ...11 26 MELSEC A 11 MANUAL CONTROL MEMO...
Page 576: ...12 104 MELSEC A 12 CONTROL AUXILIARY FUNCTIONS MEMO...
Page 745: ......