12 - 101
MELSEC-A
12 CONTROL AUXILIARY FUNCTIONS
(3) Control details and setting
The following shows the control details and setting when the indirectly
specification data set to the indirectly specification No. 8001 of axis 1 is started.
1150
Y10
4500
PLC CPU
8001
1
1
2
4
ON
3
AD75
Input/output signal
Servo amplifier
Buffer memory
Controlled with
the specified
positioning data
: When making a positioning start at
the scan next to positioning completion,
provide X1 as an interlock to make
a start after Y10 is turned OFF and
X1 then turns OFF.
1) Set "8001" to "
Cd.11
Positioning start No.".
2) Set the positioning data No. to the "indirectly specification data" to be started. (In this case, set "1".)
3) Turn ON the start signal.
4) The positioning data set to the "positioning data No. for indirectly specification No. 8001" is started.
Fig. 12.46 Indirectly specification function operating procedure (for axis 1)
Summary of Contents for A1SD75M1
Page 2: ......
Page 20: ...A 18 MEMO...
Page 22: ...MEMO...
Page 27: ...1 5 MELSEC A 1 PRODUCT OUTLINE MEMO...
Page 42: ...1 20 MELSEC A 1 PRODUCT OUTLINE MEMO...
Page 52: ...2 10 MELSEC A 2 SYSTEM CONFIGURATION MEMO...
Page 111: ...5 21 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 115: ...5 25 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 123: ...5 33 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 127: ...5 37 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 167: ...5 77 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 193: ...5 103 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 276: ...5 186 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 332: ...7 18 MELSEC A 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO...
Page 334: ...MEMO...
Page 422: ...9 64 MELSEC A 9 MAIN POSITIONING CONTROL MEMO...
Page 446: ...10 24 MELSEC A 10 ADVANCED POSITIONING CONTROL MEMO...
Page 472: ...11 26 MELSEC A 11 MANUAL CONTROL MEMO...
Page 576: ...12 104 MELSEC A 12 CONTROL AUXILIARY FUNCTIONS MEMO...
Page 745: ......