14 - 66
MELSEC-A
14 TROUBLESHOOTING
Division of
warning
Warning
code
Warning name
Description
Action at occurrence of warning
112
Illegal override
value
A value outside the range from 1 to 300 is
specified as an override value.
•
Setting “0”: Controlled to 100.
•
“301” or larger setting: Controlled to 300.
113
Outside new
torque value
range
A value outside the range from 1 to 500 is
specified as a new torque value.
Torque change is not carried out.
114
Below bias
speed
The command speed is smaller than the
starting bias speed.
Operation is made at the bias speed at start.
115
Illegal No. of
read/write data
The No. of read/write data of positioning data
No. 101 to 600 is outside the range from 1 to
100.
•
The warning is for the target axis.
•
Reading/writing is not made.
Common
116
Parameter
transmission
failure
When the PLC READY signal [Y1D] turned
from OFF to ON, parameter transmission to the
servo amplifier failed.
The warning is for the target axis.
300
Speed change
during
deceleration
A speed change request is issued during
deceleration and stop caused by turned OFF of
the JOG start signal.
Speed change is not made.
JOG
301
JOG speed limit
value
The new speed value in JOG operation
exceeds the JOG speed limit value.
•
If the JOG speed limit value is exceeded,
JOG operation continues at the JOG speed
limit value.
•
The “in speed limit flag” is turned ON while
the JOG speed limit is active.
401
Outside manual
pulse generator
input
magnification
The manual pulse generator 1 pulse input
magnification is “0” or equal to or larger than
“101.”
•
Input magnification
≥
101: 100
•
Input magnification “0”: 1
Manual
pulse
generator
402
Manual pulse
generator
selection 0
The manual pulse generator enable flag is set
when “manual pulse generator selection” in
detail parameter 1 is set at “0.”
Failure to start manual pulse generator
operation
Summary of Contents for A1SD75M1
Page 2: ......
Page 20: ...A 18 MEMO...
Page 22: ...MEMO...
Page 27: ...1 5 MELSEC A 1 PRODUCT OUTLINE MEMO...
Page 42: ...1 20 MELSEC A 1 PRODUCT OUTLINE MEMO...
Page 52: ...2 10 MELSEC A 2 SYSTEM CONFIGURATION MEMO...
Page 111: ...5 21 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 115: ...5 25 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 123: ...5 33 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 127: ...5 37 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 167: ...5 77 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 193: ...5 103 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 276: ...5 186 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 332: ...7 18 MELSEC A 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO...
Page 334: ...MEMO...
Page 422: ...9 64 MELSEC A 9 MAIN POSITIONING CONTROL MEMO...
Page 446: ...10 24 MELSEC A 10 ADVANCED POSITIONING CONTROL MEMO...
Page 472: ...11 26 MELSEC A 11 MANUAL CONTROL MEMO...
Page 576: ...12 104 MELSEC A 12 CONTROL AUXILIARY FUNCTIONS MEMO...
Page 745: ......