3 - 13
MELSEC-A
3 SPECIFICATIONS AND FUNCTIONS
3.4.2 Details of input signals (AD75
PLC CPU)
The ON/OFF timing and conditions, etc., of the input signals are shown below.
Device
No.
Signal name
Details
X0 AD75
READY
OFF
:
READY
complete
ON : Not
ready/WDT
error
•
When the PLC READY signal [Y1D] turns from OFF to ON, the parameter setting
range is checked, and if there is no error, this signal turns OFF.
•
When the PLC READY signal [Y1D] turns OFF, this signal turns ON.
•
When a WDT error occurs, this signal turns ON.
•
This is used for the interlock with the sequence program, etc.
OFF
ON
ON
OFF
PLC READY signal
[Y1D]
AD75 READY signal
[X0]
X1
X2
X3
Axis 1
Axis 2
Axis 3
Start
complete
OFF : Starting
incomplete
ON : Start
complete
•
When the positioning start signal turns ON, and the AD75 starts the positioning
process, this signal turns ON.
(The start complete signal also turns ON during zero point return control.)
OFF
ON
OFF
ON
Positioning start signal
[Y10]
Start complete signal
[X1]
X4
X5
X6
Axis 1
Axis 2
Axis 3
BUSY *1
OFF : Not BUSY
ON : BUSY
•
This signal turns ON at the start of positioning, zero point return or JOG, and turns
OFF after the " Da.8 Dwell time" has passed after positioning stop. (This signal
remains ON during positioning.) This signal turns OFF when stopped with step
operation.
•
During manual pulse generator operation, this signal turns ON while the " Cd.22
Manual pulse generator enable flag" is ON.
•
This signal turns OFF at an error complete or stop.
X7
X8
X9
Axis 1
Axis 2
Axis 3
Positioning
complete *2
OFF : Positioning
incomplete
ON : Positioning
complete
•
This signal turns ON for the time set in " Pr.41 Positioning complete signal output
time" from the time that each positioning data No. positioning control is completed.
(This does not turn ON when " Pr.41 Positioning complete signal output time" is 0.)
•
If positioning is started (including zero point return), JOG operation or manual pulse
generator operation start is executed while this signal is ON, the signal will turn OFF.
•
This signal will not turn ON when speed control or positioning is canceled midway.
XA
XB
XC
Axis 1
Axis 2
Axis 3
Error
detection
OFF : No error
ON : Error
occurrence
•
This signal turns ON when an error listed in section 14.1 occurs, and turns OFF
when the error is reset.
XD
XE
XF
Axis 1
Axis 2
Axis 3
M code ON OFF : No M code
setting
ON : M code set
•
In the WITH mode, this signal turns ON when the positioning data is started, and in
the AFTER mode, this signal turns ON when the positioning data positioning is
completed.
•
This signal turns OFF with the " Cd.14 M code OFF request".
•
When there is no M code designated (when " Da.9 M code" is 0), this signal will
remain OFF.
•
With using continuous path control for the positioning operation, the positioning will
continue even when this signal does not turn OFF. However, a warning will occur.
(Warning code: 503)
•
When the PLC READY signal [Y1D] turns OFF, the M code ON signal will also turn
OFF.
•
If operation is started while the M code is ON, an error will occur. (Error code: 536)
Important
*1 When position control of movement amount 0 is executed, the BUSY signal also turns ON. However,
since the ON time is short, the ON status may not be detected in the sequence program.
*2 AD75 positioning complete refers to when the output of position/speed commands from AD75 is
completed.
Thus, even if the AD75 positioning complete signal turns ON, the system may continue to operate.
Summary of Contents for A1SD75M1
Page 2: ......
Page 20: ...A 18 MEMO...
Page 22: ...MEMO...
Page 27: ...1 5 MELSEC A 1 PRODUCT OUTLINE MEMO...
Page 42: ...1 20 MELSEC A 1 PRODUCT OUTLINE MEMO...
Page 52: ...2 10 MELSEC A 2 SYSTEM CONFIGURATION MEMO...
Page 111: ...5 21 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 115: ...5 25 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 123: ...5 33 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 127: ...5 37 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 167: ...5 77 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 193: ...5 103 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 276: ...5 186 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 332: ...7 18 MELSEC A 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO...
Page 334: ...MEMO...
Page 422: ...9 64 MELSEC A 9 MAIN POSITIONING CONTROL MEMO...
Page 446: ...10 24 MELSEC A 10 ADVANCED POSITIONING CONTROL MEMO...
Page 472: ...11 26 MELSEC A 11 MANUAL CONTROL MEMO...
Page 576: ...12 104 MELSEC A 12 CONTROL AUXILIARY FUNCTIONS MEMO...
Page 745: ......