7-30
Chapter 7
Wire Connection and Optional Devices
Output terminals
(Wiring example)
AL:[AL] 16:[ZS]
○
X
: Devices such as lamp, relay, PLC
○
RY
: Relay
・
[ ] indicates the factory default setting.
Initial terminal function
[RUN:001] During operation signal
・
Turns ON during operation (PWM output).
[FA1:002] Frequency reached signal
・
Turns ON when the output frequency reaches the
command frequency.
[FA2:003] Frequency reached signal 2
・
Turns ON when the output frequency reaches the set
frequency [CE-10]-[CE-13].
[IRDY:007] Operation ready completion
・
Turns ON when operation is ready.
[OL:035] Overload advance notice
・
Turns ON when current exceeds the level of overload
advance notice.
[ZS:040] 0 Hz detection signal
・
Turns ON when the output frequency goes below the
0-Hz detection value level [CE-33].
* Make sure to use diode. Otherwise, the internal
circuit may be damaged.
About [AL] operation
・
When [CC-17] = 00
Power supply
Status
AL0-AL1
AL0-AL2
ON
Normal
Open
Close
ON
Trip
Close
Open
OFF
–
Open
Close
・
When [CC-17] = 01
Power supply
Status
AL0-AL1
AL0-AL2
ON
Normal
Close
Open
ON
Trip
Open
Close
OFF
–
Open
Close
Terminal
symbol
Terminal
name
Description
Electrical characteristics
O
u
tp
u
t
te
rm
in
a
l
D
ig
it
a
l
o
u
tp
u
t
O
p
e
n
c
o
lle
c
to
r
15,14
13,12
11
Output
terminal
You can select terminal functions
using the parameter settings
corresponding to each terminal.
These terminals can be used both
in sink logic or source logic.
Open collector output
・
Between each terminal and CM2
・
Voltage drop at ON: 4V or below
・
Maximum allowable voltage: 27V
・
Maximum allowable current: 50mA
CM2
Common
for
output
terminal
Common terminals for output
terminals 11-15
R
e
la
y
16A
16C
1a relay
terminal
A relay for contact A output.
Maximum capacity of contact
・
AC250V, 2A (resistance)/AC250V,
1A (induction)
Minimum capacity of contact
・
DC1V ,1mA
AL0
AL1
AL2
1c relay
terminal
A relay for contact C output.
Maximum capacity of contact
AL1/AL0
:
・
AC250V, 2A (resistance)/AC250V,
0.2A (induction)
AL2/AL0
:
・
AC250V, 1A (resistance)/
・
AC250V,
0.2A (induction)
Minimum capacity of contact (common)
・
AC100V, 10mA/DC5V ,100mA
16A
16C
Relay output
terminal
X
AL2
AL1
AL0
Alarm relay output
terminal
X
11
[RUN]
12
[FA1]
13
[FA2]
14
[IRDY]
15
[OL]
CM2
Output terminals
RY
RY
RY
RY
RY
Control circuit terminal area
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...