12-4-16
Chapter 12
Inverter Functions
12.4.12
Remote operation of frequency
• Want to change the frequency of the motor using
signal input.
• Want to change the frequency fusing a remote
external button.
• Want to change the PID target value fusing a
remote external button.
UP/DOWN function
• The frequency command of the inverter can be
changed by a signal input if 020 [FUP terminal and
021 [FDN] terminal are assigned in the input
terminal function.
•
This function works following the selected
frequency command when the frequency command
selection [AA101] is 07 (parameter effective) or
when a multi-step speed command is given.
• The command operation time with the terminals
020[FUP]/021[FDN] being ON follows the
acceleration time [CA-64] to increase or the
deceleration time [CA-66] to decrease.
Action chart
(For the case where the frequency command comes
with the parameter setting and multi-step speed
function)
• When 020 [FUP] terminal / 021 [FDN] terminal is
made ON/OFF immediately after the power
shutdown, data may not be able to be correctly
saved.
• Cannot be used to set the frequency of the input
terminal function 029 [JG] jogging operation.
• Even when 024 [SET] function is used to switch to
the second control, the operation time follows the
acceleration time [CA-64] to increase or the
deceleration time [CA-66] to decrease.
• If 01 (save) is chosen in [CA-61], the frequency
value adjusted by the 020 [FUP] terminal / 021
[FDN] function can be saved. To clear the saved
frequency value, assign 022[UDC] to the input
terminal and change the [UDC] terminal from ON to
OFF. Clearance by [UDC] follows the designated
value of [CA-62].
Q
A
!
Operation
command.
(FW,RV)
FUP
FDN
If [FUP] and [FDN] terminals are made ON
simultaneously, acceleration/deceleration is
not made.
Frequency
command
Output
frequency
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...