20-2
Chapter 20
Specifications
20.2 Inverter Specifications
20.2.1
200V Class Specifications
*1)
The values shown are ratings when carrier frequency is at 2kHz.
Please
use the inverter in accordance with "20.4 Current Derating Table".
*2)
The rated input currents shown in the table are the values when the rated
current is output.
The values vary depending on impedance on the
power supply (wiring, breaker, input reactor option, etc.)
*3)
The following shows response to the Low Voltage Directive.
- Pollution degree 2
- Overvoltage category 3
*4)
The power supply equipment capacities shown in the table are the
values when 220V rated current is output.
The values vary depending on
impedance on the power supply (wiring, breaker, input reactor option,
etc.)
*5)
The setting of rated values for carrier frequencies [bb101]/[bb201] are
internally limited in accordance with the description.
Also, it is
recommended to set values equivalent to or above (maximum output
frequency for driving ×10) Hz for the setting of carrier frequencies
[bb101]/[bb201]. Also, in the case of induction motor (IM) control, for
items other than those subject to V/f control, it is recommended to set
carrier frequency at 2kHz or more. In the case of synchronous motor
(SM)/permanent magnet motor (PMM) control, it is recommended to set
carrier frequency at 8kHz or more.
* The models in 200V class are shown as P1-*****-LFF or
P1-*****-LFUF. The portion "*****" are filled with numbers
described in "Model symbol".
*6)
Values when sensorless vector control is applied at ND rating on a
Hitachi's standard motor.
Torque characteristics may be different
depending on the control method or motor for use.
*7)
The dimensions do not include buttons on the operator keypad.
When optional items are connected, the required dimensions will
increase. Check the instruction manuals of each optional item for details.
Model symbol
P1-*****-L
00044 00080 00104 00156 00228 00330 00460 00600 00800 00930 01240 01530 01850 02290 02950
ND capacity standard notation
P1-***L
004
007
015
022
037
055
075
110
150
185
220
300
370
450
550
Applicable motor (4-pole) capacity (kW)
VLD
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
LD
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
ND
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
Output
Rated output current (A)
VLD
4.4
8.0
10.4
15.6
22.8
33.0
46.0
60.0
80.0
93.0
124
153
185
229
295
LD
3.7
6.3
9.4
12.0
19.6
30.0
40.0
56.0
73.0
85.0
113
140
169
210
270
ND
3.2
5.0
8.0
11.0
17.5
25.0
32.0
46.0
64.0
76.0
95.0
122
146
182
220
Overload current rating *1)
VLD
110% 60sec / 120% 3sec
LD
120% 60sec / 150% 3sec
ND
150% 60sec / 200% 3sec
Rated output voltage
3-phase (3-wire) 200-240V (depending on receiving voltage)
Rated capacity
(kVA)
200V
VLD
1.5
2.8
3.6
5.4
7.9
11.4
15.9
20.8
27.7
32.2
43.0
53.0
64.1
79.3 102.2
LD
1.3
2.2
3.3
4.2
6.8
10.4
13.9
19.4
25.3
29.4
39.1
48.5
58.5
72.7
93.5
ND
1.1
1.7
2.8
3.8
6.1
8.7
11.1
15.9
22.2
26.3
32.9
42.3
50.6
63.0
76.2
240V
VLD
1.8
3.3
4.3
6.5
9.5
13.7
19.1
24.9
33.3
38.7
51.5
63.6
76.9
95.2 122.6
LD
1.5
2.6
3.9
5.0
8.1
12.5
16.6
23.3
30.3
35.3
47.0
58.2
70.3
87.3 112.2
ND
1.3
2.1
3.3
4.6
7.3
10.4
13.3
19.1
26.6
31.6
39.5
50.7
60.7
75.7
91.5
Input
Rated input current (A) *2)
VLD
5.2
9.5
12.4
18.6
27.1
39.3
54.8
71.4
95.2 110.7 147.6 182.1 220.2 272.6 351.2
LD
4.4
7.5
11.2
14.3
23.3
35.7
47.6
66.7
86.9 101.2 134.5 166.7 201.2 250.0 321.4
ND
3.8
6.0
9.5
13.1
20.8
29.8
38.1
54.8
76.2
90.5 113.1 145.2 173.8 216.7 261.9
Rated input AC voltage *3)
Control power supply: Power supply single phase 200-240V/allowable variation range 170-264V,
50Hz (allowable variation range: 47.5~52.5Hz)/60Hz (allowable variation range: 57-63Hz)
Main circuit power supply: 3-phase (3-wire) 200-240V/allowable variation range 170-264V,
50Hz (allowable variation range: 47.5-52.5Hz)/60Hz (allowable variation range: 57-63Hz)
Power supply equipment
capacity (kVA) *4)
VLD
2.0
3.6
4.7
7.1
10.3
15.0
20.9
27.2
36.3
42.2
56.3
69.4
83.9 103.9 133.8
LD
1.7
2.9
4.3
5.4
8.9
13.6
18.1
25.4
33.1
38.6
51.3
63.5
76.7
95.3 122.5
ND
1.5
2.3
3.6
5.0
7.9
11.3
14.5
20.9
29.0
34.5
43.1
55.3
66.2
82.6
99.8
Carrier frequency operating range *5)
VLD
0.5~10.0kHz
LD
0.5~12.0kHz
ND
0.5~16.0kHz
Motor start torque*6)
200%/0.3Hz
Braking
Regenerative braking
Equipped with BRD circuit (with a discharging resistor separately installed)
Regenerative braking unit
separately installed
Minimum resistance that can be
connected (Ω)
50
50
35
35
35
16
10
10
7.5
7.5
5
-
-
-
-
Dimension
*7)
H (height) (mm)
255
255
255
255
255
260
260
260
390
390
390
540
550
550
700
W (width) (mm)
150
150
150
150
150
210
210
210
245
245
245
300
390
390
480
D (depth) (mm)
140
140
140
140
140
170
170
170
190
190
190
195
250
250
250
Protective construction
IP20 / UL open type
Approximate mass (kg)
3
3
3
3
3
7
7
7
16
16
16
22
30
30
43
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...