Appendix 1-29
Appendix 1
List of Parameters
*1) P1-01760-H (P1-750H) to P1-03160-H (P1-1320H) shall
be as follows.
[Ub-03]=02: 0.5~10.0 (kHz)
[Ub-03]=00 or 01: 0.5~8.0 (kHz)
Code
Name
Data range
Initial value
Note
Page
bb-43
Restarting level of frequency acquisition
(0.00 to 2.00)
× Inverter rated current (A)
1.00
× Inverter
rated current
12-14-6
bb-44
Constant (frequency) for frequency
acquisition restarting
0.10~30.00 (s)
0.50
12-14-6
bb-45
Constant (voltage) for frequency
acquisition restarting
0.10~30.00 (s)
0.50
12-14-6
bb-46
Overcurrent suppression level for
frequency pull-in restart
(0.20 to 2.00)
× Inverter rated current (A)
1.00
× Inverter
rated current
12-14-6
bb-47
Start frequency selection for frequency
pull-in restart
00 (Cutoff frequency)/
01 (Maximum frequency)/
02 (Setting frequency)
00
12-14-6
bb160
First overcurrent detection level
(0.20 to 2.20)
x Inverter ND rated current
2.20
× Inverter ND
rated current
12-16-5
bb-61
Excessive voltage of accepted power
00 (Warning)/01 (Error)
00
bb-62
Incoming overvoltage level selection
(200V class) 300.0 - 410.0 (V)
(400V class) 600.0 - 820.0 (V)
(200 V class) 390.0
(400V class) 780.0
bb-64
Ground fault detection selection
00 (Disabled)/01 (Enabled)
01
18-15
bb-65
Input phase loss selection
00 (Disabled)/01 (Enabled)
00
12-16-1
bb-66
Output phase loss selection
00 (Disabled)/01 (Enabled)
00
12-16-2
bb-67
Output phase loss detection sensitivity
1~100 (%)
10
12-16-2
bb-70
Thermistor error level
0~10000
(Ω)
3000
bb-80
Over-speed error detection level setting
0.0~150.0 (%)
135.0
12-16-12
bb-81
Over-speed error detection time
0.0~5.0 (s)
0.5
12-16-12
bb-82
Operation for speed deviation error
00 (Warning)/01 (Error)
00
12-16-11
bb-83
Speed deviation error detection level
setting
0.0~100.0 (%)
15.0
12-16-11
bb-84
Speed deviation error detection time
0.0~5.0 (s)
0.5
12-16-11
bb-85
Behavior when the position deviation is
abnormal
00 (Warning)/01 (Error)
00
12-17-18
bb-86
Abnormal position deviation detection
level
0.0~65535 (×100pls)
4096
12-17-18
bb-87
Abnormal position deviation time
0.0~5.0 (s)
0.5
12-17-18
bb201
Second carrier frequency
[Ub-03]=02: Normal duty
0.5~16.0 (kHz)
[Ub-03]=01: Low duty
0.5~12.0 (kHz)
[Ub-03]=00: Very low duty
0.5~10.0 (kHz)
*1)
2.0
12-17-1
bb202
Second sprinkle carrier pattern selection
00 (Disabled)/
01 (Pattern 1 enabled)/
02 (Pattern 2 enabled)/
03 (Pattern 3 enabled)/
00
12-17-1
bb203
Second automatic carrier frequency
reduction selection
00 (Disabled)/
01 (Enabled: current)/
02 (Enabled: temperature)
00
12-17-1
bb260
Second overcurrent detection level
(0.20 to 2.20)
x Inverter ND rated current
2.20
× Inverter
rated current
12-17-1
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...