14-53
Chapter 14
RS485 Communication
Function
Code
Register
No.
(decimal)
Register
No.
(hexadecimal)
Function Name
R/W
Monitor Content and
Setting Item
Data
Resolution /
Unit
bA101
13001
32C9h
First frequency upper limit selection
R/W 0 ~ 13
1
bA102
13002
32Cah
First frequency upper limiter
R/W 0 ~ 59000
0.01Hz
bA103
13003
32CBh
First frequency lower limiter
R/W 0 ~ 59000
0.01Hz
bA110
13010
32D2h
First torque limit selection
R/W 0 ~ 11
1
bA111
13011
32D3h
First torque limit parameter mode selection
R/W 0 ~ 1
1
bA112
13012
32D4h
First torque limit 1 (Four quadrant normal
powered)
R/W 0 ~ 5000
0.1%
bA113
13013
32D5h
First torque limit 2 (Four quadrant reverse
regenerative)
R/W 0 ~ 5000
0.1%
bA114
13014
32D6h
First torque limit 3 (Four quadrant reverse
powered)
R/W 0 ~ 5000
0.1%
bA115
13015
32D7h
First torque limit 4 (Four quadrant normal
regenerative)
R/W 0 ~ 5000
0.1%
bA116
13016
32D8h
First torque LAD stop selection
R/W 0 ~ 1
1
bA120
13020
32DCh
First overcurrent suppression selection
R/W 0 ~ 1
1
bA121
13021
32DDh
First overcurrent suppression level
R/W
(0 to 2.00) * CTL rated
current
0.1A
bA122
13022
32Deh
First overload limit 1 selection
R/W 0 ~ 3
1
bA123
13023
32DFh
First overload limit 1 level
R/W
(0.20 to 2.00) * CTL
rated current
0.1A
bA124
13024
32E0h
First overload limit 1 operation
time
(High)
R/W 10 ~ 360000
0.01s
(bA125)
13025
32E1h
(Low)
bA126
13026
32E2h
First overload limit 2 selection
R/W 0 ~ 3
1
bA127
13027
32E3h
First overload limit 2 level
R/W
(0.20 to 2.00) * CTL
rated current
0.1A
bA128
13028
32E4h
First overload limit 2 operation
time
(High)
R/W 10 ~ 360000
0.01s
(bA129)
13029
32E5h
(Low)
bA-30
13030
32E6h
Instantaneous power failure non-stop
selection
R/W 0 ~ 3
1
bA-31
13031
32E7h
Instantaneous power failure non-stop
function starting voltage
R/W
200V class: 0 ~ 4100
400V class: 0 ~ 8200
0.1Vdc
bA-32
13032
32E8h
Instantaneous power failure non-stop target
level
R/W
200V class: 0 ~ 4100
400V class: 0 ~ 8200
0.1Vdc
bA-34
13034
32Eah
Instantaneous power failure
non-stop deceleration time
(High)
R/W 1 ~ 360000
0.01s
(bA-35)
13035
32Ebh
(Low)
bA-36
13036
32Ech
Instantaneous power failure non-stop
deceleration starting range
R/W 0 ~ 1000
0.01Hz
bA-37
13037
32Edh
Instantaneous power failure non-stop
constant DC voltage control P gain
R/W 0 ~ 500
0.01
bA-38
13038
32Eeh
Instantaneous power failure non-stop
constant DC voltage control I gain
R/W 0 ~ 15000
0.01s
bA140
13040
32F0h
First overvoltage suppression function
selection
R/W 0 ~ 3
1
bA141
13041
32F1h
First overvoltage suppression level setting
R/W
200V class: 3300 ~
4000
400V class: 6600 ~
8000
0.1Vdc
bA142
13042
32F2h
First overvoltage suppression
operating time
(High)
R/W 0 ~ 360000
0.01s
(bA143)
13043
32F3h
(Low)
bA144
13044
32F4h
First constant DC voltage control P gain
R/W 0 ~ 500
0.01
bA145
13045
32F5h
First constant DC voltage control I gain
R/W 0 ~ 15000
0.01s
bA146
13046
32F6h
First overexcitation function selection (V/f)
R/W 0 ~ 4
1
bA147
13047
32F7h
First overexcitation output filter
time constant (V/f)
R/W 0 ~ 100
0.01s
bA148
13048
32F8h
First overexcitation voltage gain (V/f)
R/W 50 ~ 400
1%
bA149
13049
32F9h
First overexcitation suppression level setting
(V/f)
R/W
200V class: 3300 ~
4000
400V class: 6600 ~
8000
0.1Vdc
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...