Appendix 1-47
Appendix 1
List of Parameters
*1)
Varies depending on inverter models and settings of
duty rating.
Code
Name
Data range
Initial value
Note
Page
Hb102
First IM motor capacity selection
0.01~160.00 (kW)
*1)
Hb103
Selection of number of first IM motor
poles
2 to 48 (poles)
4
Hb104
First IM base frequency
10.00~590.00 (Hz)
60.00 (*FF, *FUF)/
50.00 (*FEF, *FCF)
Hb105
First IM maximum frequency
10.00~590.00 (Hz)
60.00 (*FF, *FUF)/
50.00 (*FEF, *FCF)
Hb106
First IM motor's rated voltage
1~1000 (V)
200 V class: 200 (*FF)/
230 (*FEF, *FUF, *FCF)
400V class:
400 (*FF, *FEF, *FCF)/
460 (*FUF)
Hb108
First IM motor's rated current
0.01~10000.00 (A)
*1)
Hb110
First IM motor constant R1
0.000001~1000.000000
(Ω)
*1)
Hb112
First IM motor constant R2
0.000001~1000.000000
(Ω)
*1)
Hb114
First motor constant L
0.000001~1000.000000 (mH)
*1)
Hb116
First IM motor constant Io
0.01~10000.00 (A)
*1)
Hb118
First IM motor constant J
0.00001~10000.00000 (kgm2)
*1)
Hb130
First minimum frequency
0.10~10.00 (Hz)
0.50
12-14-1
Hb131
First reduced voltage start time
0~2000 (ms)
36
12-14-1
Hb140
First manual torque boost operation
mode selection
00 (Disabled)/
01 (Always enabled)/
02 (Enabled only for forward
revolution)/
03 (Enabled only for reverse
revolution)
01
12-9-8
Hb141
First amount of manual torque boost 0.0~20.0 (%)
0.0
12-9-8
Hb142
First manual torque boost break
point
0.0~50.0 (%)
0.0
12-9-8
Hb145
First energy-saving operation
selection
00 (Disabled)/01 (Enabled)
00
12-9-7
Hb146
First energy-saving
response/accuracy adjustment
0.0~100.0(%)
50.0
12-9-7
Hb150
First free V/f frequency 1
0.00~[Hb152] (Hz)
0.00
12-9-6
Hb151
First free V/f voltage 1
0.0~1000.0 (V)
0.0
Hb152
First free V/f frequency 2
[Hb150]~[Hb154] (Hz)
0.00
Hb153
First free V/f voltage 2
0.0~1000.0 (V)
0.0
Hb154
First free V/f frequency 3
[Hb152]~[Hb156] (Hz)
0.00
Hb155
First free V/f voltage 3
0.0~1000.0 (V)
0.0
Hb156
First free V/f frequency 4
[Hb154]~[Hb158] (Hz)
0.00
Hb157
First free V/f voltage 4
0.0~1000.0 (V)
0.0
Hb158
First free V/f frequency 5
[Hb156]~[Hb160] (Hz)
0.00
Hb159
First free V/f voltage 5
0.0~1000.0 (V)
0.0
Hb160
First free V/f frequency 6
[Hb158]~[Hb162] (Hz)
0.00
Hb161
First free V/f voltage 6
0.0~1000.0 (V)
0.0
Hb162
First free V/f frequency 7
[Hb160]~[Hb104] (Hz)
0.00
Hb163
First free V/f voltage 7
0.0~1000.0 (V)
0.0
Hb170
First slip compensation P gain with
sensor (V/f with sensor)
0~1000 (%)
100
12-9-27
Hb171
First slip compensation I gain with
sensor (V/f with sensor)
0~1000 (%)
100
12-9-27
Hb180
First output voltage gain
0~255 (%)
100
12-9-11
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...