19-5
Chapter 19
Maintenance and Inspection
19.6 Checking Method of Inverter and
Converter.
・
Using a tester, you can check the condition of
inverter and converter if it is good or bad.
(preparation)
(i) Remove the power lines connected from an
external source (R, S, T), wires connecting to the
motor (U, V, W), and regenerative braking resistor
(P, RB).
(ii)
Prepare a tester. (The range used is 1Ω
resistance measurement range.)
(Checking method) *1)
・
You can determine the good-or-bad condition of
conduction status of terminals on the inverter main
circuit terminal block R, S, T, U, V, W, RB, P, and N
by alternately changing the polarity of tester for
measurement.
Tester polarity
Measured
value *2)
(Red)
(Black)
C
o
n
v
e
rt
e
r
D1
R
PD
Non-conductive
PD
R
Conductive
D2
S
PD
Non-conductive
PD
S
Conductive
D3
T
PD
Non-conductive
PD
T
Conductive
D4
R
N
Conductive
N
R
Non-conductive
D5
S
N
Conductive
N
S
Non-conductive
D6
T
N
Conductive
N
T
Non-conductive
In
v
e
rt
e
r
TR1
U
P
Non-conductive
P
U
Conductive
TR2
V
P
Non-conductive
P
V
Conductive
TR3
W
P
Non-conductive
P
W
Conductive
TR4
U
N
Conductive
N
U
Non-conductive
TR5
V
N
Conductive
N
V
Non-conductive
TR6
W
N
Conductive
N
W
Non-conductive
BRD TR7
RB
P
Non-conductive
P
RB
Conductive
RB
N
Non-conductive
N
RB
Non-conductive
*1)
By measuring the voltage between P and N in the DC
voltage range, check that electricity is fully discharged
from the smoothing capacitor before performing check.
*2)
When electricity is not conducted, a nearly infinite
value is demonstrated.
Due to effects of the smoothing
capacitor, electricity may be conducted instantly, not
showing an infinite value. When electricity is conducted,
a numeric value range will be indicated from some to
dozens in a unit of
Ω. The values vary depending on
the element type, tester, type, etc. However, it is
acceptable if numeric values obtained for each item
are nearly the same. The measured value may be
varied some degree in
Ω by the reason of the
preventing inrush current of current limiting resistor.
*3)
The braking circuit (BRD) section is equipped as
standard on the following models: P1-00044-L -
P1-01240-L (P1-004L~P1-220L) and P1-00041-H -
P1-00930-H (P1-007H~P1-370H)
Converter
Inverter
PD
D1
D4
D2
D5
D3
D6
R
S
T
TR4
TR5
TR6
TR1
TR2
TR3
C +
P
N
TR7
RB
U
V
W
Braking resistor circuit (BRD) *3)
Converter
Inverter
PD
D1
D4
D2
D5
D3
D6
R
S
T
TR4
TR5
TR6
TR1
TR2
TR3
C +
P
N
TR7
RB
U
V
W
Braking resistor circuit (BRD) *3)
Model (P1-*****-*)
200V class: 00044-L (004L) - 00600-L (110L)
400V class: 00041-H (007H) - 00310-H (110H)
Model (P1-*****-*)
200V class: 00800-L (150L) - 02950-L (550L)
400V class: 00400-H (150H) - 03160-H (1320H)
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...