Appendix 1-25
Appendix 1
List of Parameters
*1) The minimum resistance varies depending on inverter
models.
Code
Name
Data range
Initial value
Note
Page
bA-30
Instantaneous power failure
non-stop selection
00 (Disabled)/
01 (Enabled: deceleration stop)/
02 (Enabled: no recovery)/
03 (Enabled: with recovery)
00
12-13-17
bA-31
Instantaneous power failure
non-stop function starting voltage
(200V class) 0.0 - 410.0 (V)
(400V class) 0.0 - 820.0 (V)
(200 V class) 220.0
(400V class) 440.0
12-13-17
bA-32
Instantaneous power failure
non-stop target level
(200V class) 0.0 - 410.0 (V)
(400V class) 0.0 - 820.0 (V)
(200 V class) 360.0
(400V class) 720.0
12-13-17
bA-34
Instantaneous power failure
non-stop deceleration time
0.01~3600.00 (s)
1.00
12-13-17
bA-36
Instantaneous power failure
non-stop deceleration starting
range
0.00~10.00 (Hz)
0.00
12-13-17
bA-37
Instantaneous power failure
non-stop constant DC voltage
control P gain
0.00~5.00
0.20
12-13-17
bA-38
Instantaneous power failure
non-stop constant DC voltage
control I gain
0.00~150.00 (s)
1.00
12-13-17
bA140
First overvoltage suppression
function
00 (Disabled)/
01 (DC voltage constant deceleration)
02 (Acceleration only at deceleration)/
03 (Acceleration at constant
speed/deceleration)
00
12-13-4
bA141
First overvoltage suppression
level setting
(200V class) 330.0 - 400.0 (V)
(400V class) 660.0 - 800.0 (V)
(200 V class) 380.0
(400V class) 760.0
12-13-4
bA142
First overvoltage suppression
operating time
0.00~3600.00 (s)
1.00
12-13-4
bA144
First DC voltage control P gain
0.00~5.00
0.20
12-13-4
bA145
First DC voltage control I gain
0.00~150.00 (s)
1.00
12-13-4
bA146
First overexcitation function
selection
00 (Disabled)/
01 (Regular operation)/
02 (Operation only at deceleration)/
03 (Level mode)/
04 (Level mode only at deceleration)
02
12-13-6
bA147
First overexcitation filter time
constant
0.00~1.00(s)
0.30
12-13-6
bA148
First overexcitation voltage gain
50~400 (%)
100
12-13-6
bA149
First overexcitation control level
setting
(200V class) 330.0 - 400.0 (V)
(400V class) 660.0 - 800.0 (V)
(200 V class) 360.0
(400V class) 720.0
12-13-6
bA-60
Braking resistor operation circuit
(BRD) use rate
0.0 -
10.0×([bA-63]/minimum resistance)
2
(%)
*1)
10.0
12-13-8
bA-61
Braking resistor circuit (BRD)
selection
00 (Disabled)/
01 (Enabled: disabled at stop)/
02 (Enabled: enabled at stop)
00
12-13-8
bA-62
Braking resistor circuit (BRD) ON
level
(200V class) 330.0 - 400.0 (V)
(400V class) 660.0 - 800.0 (V)
(200 V class) 360.0
(400V class) 720.0
12-13-8
bA-63
Braking resistor circuit (BRD)
resistance
Minimum resistance -
600 (Ω)
Minimum resistance
*1)
12-13-8
bA-70
Selection of the cooling fan
operation
00 (Always ON)/
01 (ON during operation)/
02 (Temperature dependent)
00
12-18-1
bA-71
Clear cumulative operating time
of cooling fan
00 (Disabled)/01 (Clear)
00
13-17
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...