14-61
Chapter 14
RS485 Communication
Function
Code
Register
No.
(decimal)
Register
No.
(hexadecimal)
Function Name
R/W
Monitor Content and
Setting Item
Data
Resolution /
Unit
CE-40
14440
3868h
Window comparator [Ai1] upper limit level
R/W 0 ~ 100
1%
CE-41
14441
3869h
Window comparator [Ai1] lower limit level
R/W 0 ~ 100
1%
CE-42
14442
386Ah
Window comparator [Ai1] hysteresis range
R/W 0 ~ 10
1%
CE-43
14443
386Bh
Window comparator [Ai2] upper limit level
R/W 0 ~ 100
1%
CE-44
14444
386Ch
Window comparator [Ai2] lower limit level
R/W 0 ~ 100
1%
CE-45
14445
386Dh
Window comparator [Ai2] hysteresis range
R/W 0 ~ 10
1%
CE-46
14446
386Eh
Window comparator [Ai3] upper limit level
R/W -100 ~ 100
1%
CE-47
14447
386Fh
Window comparator [Ai3] lower limit level
R/W -100 ~ 100
1%
CE-48
14448
3870h
Window comparator [Ai3] hysteresis range
R/W 0 ~ 10
1%
CE-50
14450
3872h
[Ai1] operation level at disconnection
R/W 0 ~ 100
1%
CE-51
14451
3873h
[Ai1] operation level selection at
disconnection
R/W 0 ~ 2
1
CE-52
14452
3874h
[Ai2] operation level at disconnection
R/W 0 ~ 100
1%
CE-53
14453
3875h
[Ai2] operation level selection at
disconnection
R/W 0 ~ 2
1
CE-54
14454
3876h
[Ai3] operation level at disconnection
R/W -100 ~ 100
1%
CE-55
14455
3877h
[Ai3] operation level selection at
disconnection
R/W 0 ~ 2
1
CE201
24401
5F51h
Second low current signal output mode
selection
R/W 0 ~ 1
1
CE202
24402
5F52h
Second low current detection level 1
R/W
(0 to 2.00) * CTL rated
current
0.1A
CE203
24403
5F53h
Second low current detection level 2
R/W
(0 to 2.00) * CTL rated
current
0.1A
CE205
24405
5F55h
Second overload prewarning signal output
mode selection
R/W 0 ~ 1
1
CE206
24406
5F56h
Second overload prewarning level 1
R/W
(0 to 2.00) * CTL rated
current
0.1A
CE207
24407
5F57h
Second overload prewarning level 2
R/W
(0 to 2.00) * CTL rated
current
0.1A
CE220
24420
5F64h
Second over torque level (normal powered)
R/W 0 ~ 5000
0.1%
CE221
24421
5F65h
Second over torque level (reverse
regenerative)
R/W 0 ~ 5000
0.1%
CE222
24422
5F66h
Second over torque level (reverse powered)
R/W 0 ~ 5000
0.1%
CE223
24423
5F67h
Second over torque level (normal
regenerative)
R/W 0 ~ 5000
0.1%
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...