12-16-7
Chapter 12
Inverter Function
Parameter
Item
Parameter
Data
Description
Selection of
instantaneous power
failure retry
[bb-20]
0~16 / 255
Detects a decrease in the control power supply and
restarts the motor when the power supply is recovered.
When 0 is specified, the inverter immediately trips when
an instantaneous power failure occurs.
Selection of
under-voltage retry
[bb-21]
0~16 / 255
Detects a decrease in the main power supply and
restarts the motor when the power supply is recovered.
When 0 is specified, the inverter immediately trips when
an under-voltage condition occurs.
Selection of
instantaneous power
failure/under-voltage
retry
[bb-24]
00
Restarts with 0 Hz at retry.
01
Restarts with speed matching at retry.
02
Restarts with frequency pull-in at retry.
04
Restarts with speed matching at retry, and trips after
deceleration stop.
Allowable
instantaneous power
failure time
[bb-25]
0.3~25.0 (s)
Restarts if the instantaneous power failure is within the
set time.Trips if the instantaneous power failure exceeds
the specified time.
Retry wait time after
instantaneous power
failure/under-voltage
[bb-26]
0.3~100.0
(s)
Sets the time before restarting.
Selection of
instantaneous power
failure/under-voltage
trip during stopping
[bb-27]
00
Disabled
01
Enabled
02
Disabled during stopping and during deceleration stop
after the operation command has been turned off.
Selection of output
terminal function
[CC-01]~[CC-05]
017
020
021
017: Outputs [AL] Alarm signal.
020: Outputs [IP] Instantaneous power failure signal
021: Outputs [UV] Under-voltage signal.
Selection of relay
output terminal
function
[CC-06]
Selection of relay
output terminal
function
[CC-07]
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...