12-19-16
Chapter 12
Inverter Function
12.19.14
Outputting a warning based on the
amount of power-on hours
• I want to know when the number of power-on
hours reaches a certain period of time.
• I want to output with a signal the number of
operating hours of the system in which the inverter
has been incorporated.
• Assign the output terminal function 025 [ONT]
power-on time over signal to one of [CC-01] to
[CC-07] that corresponds to the output terminal
and output the signal.
• Assign 025 (ONT) to the output terminal.
• Specify the power-on time level [CE-36].
• The power-on time over signal [ONT] will be
output when the cumulative total of inverter
operating hours exceeds the time specified with
the RUN time/power-on time level [CE-36].
Parameter
• When specifying the time level as a guideline for
replacement, use a number with an adequate
margin.
• Setting example
When you want to generate a warning after the
inverter has been turned on for (300 days 24
hours 3 years =) 21,600 hours, set [CE-36] to
21,600.
Second time onward:
When you want to generate a warning after an
operation of (250 days 8 hours 5 years =)
10,000 hours, set [CE-36] to [dC-24] + 10,000.
Item
Parameter
Data
Description
Output terminal function
selection 11-15
[CC-01]~[CC-05]
025
The
power-on time over
[ONT]
is
output.
OFF: Less than or equal to the
power-on time level
ON: More than the power-on time
level
Relay output terminal
function selection 16A-16C
[CC-06]
Relay output terminal
function selection
AL1-AL0/AL2-AL0
[CC-07]
RUN time/power-on time
level
[CE-36]
0~100000[hour]
This function does not work when this
level has been set to 0.
Specify 1 to 100,000 hours.
Cumulative power-on time
monitor
[dC-24]
0~65535[hour]
The number of hours when the
inverter has been turned on is stored
for monitoring.
Q
A
!
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...
Page 781: ...Appendix 1 70 Appendix 1 List of Parameters Memo ...