12-10-7
Chapter 12
Inverter Functions
Input terminal function
Data monitor function
*1) Data range varies according to [AH-04] - [AH-06]
settings.
Item
Terminal
name
Data
Description
PID disable function
[PID]
041
Disables the PID1 function by turning ON the
terminal function. When disabled, operation is done
by using the command set for target value as
command frequency.
PID1 I control integral value clear
[PIDC]
042
Clears integral value of PID1 control.
Multi-layer target command terminal 1
[SVC1]
051
Switches multiple target values.
Multi-layer target command terminal 2
[SVC2]
052
Multi-layer target command terminal 3
[SVC3]
053
Multi-layer target command terminal 4
[SVC4]
054
PID gain switch
[PRO]
055
Switches PID gain 1 and 2 by terminal.
Item
Parameter
Data
Description
PID1 target value 1
[FA-30]
-100.00~100.00(%)*1)
Displays PID1 target value.
Is changeable when [AH-07] = 07 or
multi-layer target value 1-15 is enabled.
PID1 target value 2
[FA-32]
-100.00~100.00(%)*1)
Displays PID1 target value 2.
Is changeable when [AH-42] = 07.
PID1 target value 3
[FA-34]
-100.00~100.00(%)*1)
Displays PID1 target value 3.
Is changeable when [AH-46] = 07.
PID1 feedback monitor 1
[db-30]
-100.00~100.00(%)*1)
Displays PID1 feedback value 1.
PID1 feedback monitor 2
[db-32]
-100.00~100.00(%)*1)
Displays PID1 feedback value 2.
PID1 feedback monitor 3
[db-34]
-100.00~100.00(%)*1)
Displays PID1 feedback value 3.
PID1 target value monitor (after
calculation)
[db-42]
-100.00~100.00(%)*1)
Displays target value after calculation
by [AH-50].
PID1 feedback monitor
(After calculation)
[db-44]
-100.00~100.00(%)*1)
Displays feedback value after
calculation by [AH-54].
PID1 output monitor
[db-50]
-100.00~100.00(%)
Displays PID1 output value.
PID1 deviation monitor
[db-51]
-100.00~100.00(%)
Displays PID1 deviation.
PID1 deviation 1 monitor
[db-52]
-100.00~100.00(%)
Monitors 3 deviations of PID1 when
[AH-50] = 05 or 06.
PID1 deviation 2 monitor
[db-53]
-100.00~100.00(%)
PID1 deviation 3 monitor
[db-54]
-100.00`100.00(%)
PID current P gain monitor
[db-61]
0.0~100.0
Displays current P gain.
PID current I gain monitor
[db-62]
0.00~3600.00(s)
Displays current I gain.
PID current D gain monitor
[db-63]
0.00~100.00(s)
Displays current D gain.
PID feed-forward monitor
[db-64]
-100.00~100.00(%)
Displays feed-forward command value.
Summary of Contents for SJ Series
Page 39: ...5 4 Chapter 5 Included Items Memo ...
Page 55: ...6 16 Chapter 6 Installation Memo ...
Page 91: ...7 36 Chapter 7 Wire Connection and Optional Devices Memo ...
Page 135: ...9 40 Chapter 9 Operating Instructions Memo ...
Page 145: ...10 10 Chapter 10 Test Run Memo ...
Page 159: ...12 2 6 Chapter 12 Inverter Functions Memo ...
Page 169: ...12 3 10 Chapter 12 Inverter Functions Memo ...
Page 195: ...12 5 8 Chapter 12 Inverter Functions Memo ...
Page 217: ...12 8 12 Chapter 12 Inverter Function Memo ...
Page 287: ...12 10 32 Chapter 12 Inverter Functions Memo ...
Page 303: ...12 11 16 Chapter 12 Inverter Functions Memo ...
Page 349: ...12 15 8 Chapter 12 Inverter Function Memo ...
Page 395: ...12 17 34 Chapter 12 Inverter Functions Memo ...
Page 397: ...12 18 2 Chapter 12 Inverter Functions Memo ...
Page 415: ...12 19 18 Chapter 12 Inverter Function Memo ...
Page 581: ...15 10 Chapter 15 Optional Cassettes Memo ...
Page 591: ...16 10 Chapter 16 ProDriveNext EzSQ Memo ...
Page 642: ...18 49 Chapter 18 Tips FAQ Troubleshooting Memo ...
Page 650: ...19 8 Chapter 19 Maintenance and Inspection Memo ...